Call 1300 369 273
www.enware.com.au
before proceeding with installation
OBSTRUCTIONS
Ensure that nothing is within range of the
sensor. Any obstruction directly in front of, and
within possible range of, the sensor can trigger
the sensor randomly or constantly turn it on.
PASSING TRAFFIC
Be sure that passing traffic cannot trigger the
sensor. Allow at least 400mm clearance between
sensor and passing traffic.
REFLECTIONS AND LIGHTING
If the sensor unit is installed into a location
where a nearby wall or object is reflecting the
Infrared light back, the unit is effectively blinded
and will not operate. Up to 1.5 metre clearance
may be necessary from reflective surfaces, such
as ceramic tiles and stainless steel, directly in
front of, and parallel to, the front face of the
sensor. Any bright lighting reflecting off a highly
reflective surface such as a stainless steel sink, or
a high visibility reflective vest, may also interfere
with correct sensor operation.
Do not install sensor directly in front of a mirror.
LOCATION OF SENSOR
When selecting a location to install the wall-mounted sensor, consider the following:
SET-OUT HEIGHT
Suggested heights from finished floor:
Spout
outlet
1050mm
1120mm to point of water discharge
(Australasian Health Facility Guidelines)
Top of
basin
850mm
865mm (Australasian Health Facility Guide
-
lines)