5- COMMISSIONING OF THE energiSava 210
5.1.- For installation:
The remote control allows:
• Adjust the airflows (Minimum, kitchen boost and by-pass airflow (night cooling)
• Adjust the timing of a dirty filters (6, 9, 12 or 15 months) (factory setting 9 months)
• Adjust the balance of supply / extraction airflows (chimney or imbalance of airflow between
supply and extraction)
Adjust airflow
by-pass / cooling
Maximum
Airflow adjustment
Minimum
Airflow adjustment
5.1.a- Airflow adjustment:
Airflows depend on the configuration of the house, depending on the number of main rooms (living
room, dining room, bedroom, office, etc..) and the number of toilets and bathrooms.
Open the unit and set each potentiometer as shown in the table below according to the configuration
of the house, :
Measure the duct diameter at a maximum airflow(Boost or By-pass)
Minimum
airflow
(m
3
/h)-(l/s)
Adjustment
Qminimum
Maximum
airflow
(m
3
/h)-(l/s)
Adjustment
Qmaximum
Cooling
airflow
(m
3
/h)-(l/s)
Adjustment
Qcooling
60 - 16,7
0
120 - 33,3
0
120 - 33,3
0
75 - 20,8
1
135 - 37,5
1
135 - 37,5
1
90 - 25
2
150 - 41,7
2
150 - 41,7
2
105 - 29,2
3
165 - 45,8
3
165 - 45,8
3
120 - 33,3
4
180 - 50
4
180 - 50
4
135 - 37,5
5
195 - 54,2
5
195 - 54,2
5
-
-
210 - 58,3
6
210 - 58,3
6
potentiometers/airflows setting
13