Installation, Start-Up, Adjustment and Maintenance Manual
62
CODE GENERATED
WHEN
:
The flowmeter of the cold circuit detects water in the circuit, when (and only in such a situation) the ACF is
configured for a 2pipe coldhot plant and at that moment is operating in hot mode.
RESET METHOD
:
Reset occurs automatically when the condition that generated the code ceases.
U
80
INCOMPLETE OPERATING PARAMETERS
CODE GENERATED
BY
:
Incomplete operating parameters.
RESET METHOD
:
The Machine Code remains active until the operating parameters are entered and completed. Contact
authorised ROBUR Technical Assistance Centre.
NB: If the board is replaced, Code E 80 may appear:
this means that ACF characterisation data has not been set.
E 80
WRONG UNIT CHARACTERISATION PARAMETERS
CODE GENERATED
BY
:
Wrong unit characterisation parameters.
RESET METHOD
:
Enter and complete the ACF operating and characterisation parameters: contact authorised ROBUR
Technical Assistance Centre. Reset may be performed through the board via menu 2, menu item 1.
U
81
U
82
INVALID BANK 1 DATA INVALID BANK 2 DATA
CODE GENERATED
BY
:
Invalid Bank 1 data Invalid Bank 2 data.
RESET METHOD
:
Reset occurs automatically 5 seconds after the Machine Code is generated.
E 81 E 82
INVALID BANK 1 DATA INVALID BANK 2 DATA
CODE GENERATED
BY
:
Invalid Bank 1 data Invalid Bank 2 data.
RESET METHOD
:
Enter and complete BANK 1 and BANK 2 data via the appropriate menu: contact authorised ROBUR
Technical Assistance Centre. Reset may be performed through the board via menu 2, menu item 1.
E 84
23V TRANSFORMER OR FUSE CONNECTIONS FAULTY
CODE GENERATED
BY
:
Damage to one of the 2 fuses or one of the power cables on the 23 V~ transformer.
RESET METHOD
:
Reset may be performed through the board via menu 2, menu item 1. If the reset operation is unsuccessful,
contact ROBUR authorised Technical Assistance Centre.
E 85
INCORRECT MODULE TYPES SET
(from menu 6)
CODE GENERATED
WHEN
:
The types of module set (from menu 6) do not correspond to those managed by the board.
RESET METHOD
:
Contact authorised ROBUR Technical Assistance Centre.
E 86 E 87 E 88 E 89
MEMORY TEST UNSUCCESSFUL
CODE GENERATED
BY
:
Processor memory errors.
RESET METHOD
:
Contact authorised ROBUR Technical Assistance Centre.
E 90
AMBIENT TEMPERATURE SENSOR DEFECTIVE