Installation, Start-Up, Adjustment and Maintenance Manual
33
Figure 18
–
EXTERIOR CONTROL WIRING FOR A 230 VOLT WATER PUMP
5.3 CONTROL SWITCH WIRING
A control switch that provides an ON / OFF function is to be connected to the R and Y on the S-60
board (see Figure 15). This wiring will carry 24-volt current and it is recommended to use a cable with
the correct number of color-coded 18 gauge wires.
Fan, control, or isolation relays must have a 24-volt AC coil, which does not present more than a 0.25
amp load to the control circuit (see Figure 19, Figure 20, and Figure 21).
An isolation relay (Kit No. 18010-116)
MUST be used to separate the chiller’s transformer from
any additional equipment having a transformer or damage to the S-60 board will occur.
THERMOSTAT WIRING
Special consideration should be given to the control wiring when the chiller is used in an air
conditioning application. For details on wiring additional components, ALWAYS consult the component
manufacturer’s wiring instructions. The following diagrams give general layouts that can be used:
-
Single thermostat for heating and cooling control on a furnace. This system offers constant fan
operation at any time, even with power “OFF” to the chiller. It is readily adaptable to a furnace
that has a fan relay or can be adapted to a “heating only” furnace with the addition of a fan
relay and wiring the furnace controls as shown. Note: An isolation relay must be used in this
application.
WARNING
L1
L2
24 VOLTS
230 VOLT
WATER
PUMP
TIME DELAY RELAY
(DELAY OFF- MINIMUM 215 SECONDS)