Initial Installation
QUALIFIED INSTALLERS ONLY
v
enting
c
LeaRances
:
A
1” (25 mm)
clearance to combustibles must be maintained around any vertical vent pipe. Around a
horizontal vent pipe, the clearance to combustibles should be
2” (51 mm)
above and
1½” (38 mm)
on the sides and bottom. When combustible materials are directly above a 90° elbow,
14” (356 mm)
of clearance are necessary.
Table 4. Vent Pipe Minimum Clearances
Vertical Pipe to
the Side Walls
Horizontal Pipe to
the Sides & Bottom
Above First
Elbow
Above Subsequent
Elbows
Above Horizontal
Vent Pipe
Wall Frame 8”
(203mm) or less
Hard
Pipe
1”
(25.4 mm)
1½”
(38 mm)
14”
(356 mm)
3”
(76.2 mm)
2”
(51 mm)
10”x10”
(25x25cm)
A
10” (254 mm)
x
10” (254 mm)
frame (see Figure 29) will assure the proper support and spacing for
the vent pipe as it passes through the wall. Installations in Canada require that a wall thimble be used for
passing through walls and ceilings. All sealing and vapour barriers must comply with local building codes.
The configuration of the venting pipes depends on the locations
of walls, ceilings, and studs. However, the pipes cannot be of
arbitrary length and arrangement. Because the length of the
vertical and horizontal sections dramatically affects the burning
efficiency of the fireplace, certain guidelines have been set
in
I
nItIal
I
nstallatIon
- a
llowaBle
c
o
-a
xIal
V
ent
c
onfIguratIons
.
Venting terminals can not be recessed into a wall or siding.
WARNING: This gas appliance must not be connected
to a chimney flue serving a separate solid-burning
appliances.
Figure 29. Vent Framing For Wall or Ceiling
a
ppRoveD
v
enting
p
aRts
:
Page 26
Table 5: Approved Vent Manufacturers
Manufacturer
Brand Name
Nominal Sizes
ICC
EXCELDirect
4” x 6 5/8”
M&G Dura-Vent
Direct Vent Pro
4” x 6 5/8”
Selkirk
DIRECT-TEMP
4” x 6 5/8”
Selkirk
AMP DV
4” x 6 5/8”
Metal-Fab Inc.
Sure-Seal
4” x 6 1/2”*
This fireplace has been tested and certified
for use with the venting brand names listed
in table 5. Refer to table 6 for part numbers
of commonly used parts for both venting
systems. For more venting parts please visit
the respective manufacturers’ website.
WARNING: Do not mix parts from
different vent manufacturers’ systems.
EXCEPTION TO WARNING: This product has been evaluated by Intertek for using a DirectVent Pro
starting collar in conjunction with venting brand names listed in table 6. Use of these systems with
the DirectVent Pro starting collar is deemed acceptable and does not affect the Intertek listing of the
appliance.