hot enough to cause burns if touched by children. Non-combustible shielding or guards may be required.

3.  Termination must exhaust above the inlet elevation. It is recommended that at least five feet of vertical pipe be 

installed outside when the appliance is vented directly through a wall, to create some natural draft to prevent the 

possibility of smoke or odor during appliance shut down or power failure. This will keep exhaust from causing a 

nuisance or hazard from exposing people or shrubs to high temperatures. In any case, the safest and preferred 

venting method is to extend the vent through the roof vertically.

4.  Distance from the bottom of the termination and grade is 12” (30 cm) minimum. This is conditional upon the 

plants and nature of grade surface. The exhaust gases are hot enough to ignite grass, plants and shrubs located 

in the vicinity of termination. The grade surface must not be lawn.

5.  If the unit is incorrectly vented or the air to fuel mixture is out of balance, a slight discoloration of the exterior 

of the house might occur. Since these factors are beyond the control of Sherwood Industries Ltd, we grant no 

guarantee against such incidents.

NOTE: Venting terminals shall not be recessed into walls or siding.

Installation

v

ent

 t

ermination

 r

equirementS

:

IT IS RECOMMENDED THAT YOUR PELLET STOVE BE INSTALLED BY AN AUTHORIZED DEALER/INSTALLER. 

Figure 7: Use in conjunction with Table 2 for allowable exterior vent termination 

locations. 

Table 2: Use in conjunction with Figure 7 for allowable exterior vent termination locations. 

Letter

Minimum Clearance

Description

A

24 in (61 cm)

Above grass, top of plants, wood, or any other combustible materials.

B

48 in  (122 cm) 

Beside/below any door or window that may be opened. (18” (46 cm) if outside 

fresh air installed.) 

C

12 in (30 cm)

Above any door or window that may be opened. (9” (23 cm) if outside fresh air 

installed.) 

D

24 in (61 cm)

To any adjacent building, fences and protruding parts of the structure.

E

24 in (61 cm)

Below any eave or roof overhang

F

12 in (30 cm)

To outside corner.

G

12 in (30 cm)

To inside corner, combustible wall (vertical and horizontal terminations).

H

3 ft (91 cm) within a height 

of 15 ft (4.5 m) above the 

meter/regulator assembly

To each side of center line extended above natural gas or propane meter/

regulator assembly or mechanical vent.

I

3 ft (91 cm)

From any forced air intake of other appliance

J

12 in (30 cm)

Clearance to non-mechanical air supply inlet to building, or the combustion air 

inlet to any appliance.

K

24 in (61 cm)

Clearance above roof line for vertical terminations.

L

7 ft (2.13 m)

Clearance above paved sidewalk or paved driveway located on public property.

Air Supply Inlet

Gas Meter

Restriction Zone

(Termination not allowed)

Termination Cap

G

G

Opens

Opens

Opens

D

F

B

B

A

I

H

K

G

G

L

C

E

1. Do  not  terminate  the 

vent  in  any  enclosed  or 

semi-enclosed  areas  such 

as  a  carport,  garage, 

attic,  crawlspace,  narrow 

walkway,  closely  fenced 

area,  under  a  sundeck 

or  porch,  or  any  location 

that  can  build  up  a 

concentration  of  fumes 

such as stairwells, covered 

breezeway, etc.

2.  Vent surfaces can become 

Содержание M-55-FS

Страница 1: ...CE TECHNICAL MANUAL PELLET STOVE M 55 FS PLEASE READ THIS ENTIRE MANUAL BEFORE INSTALLATION AND USE OF THIS PELLET BURNING ROOM HEATER FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PROPERTY DAM...

Страница 2: ...aust And Fresh Air Intake Locations 10 Mobile Home Installation 11 Corner Through Wall Installation 11 Horizontal Exhaust Through Wall Installation 12 RECOMMENDED Through Wall With Vertical Rise and H...

Страница 3: ...not operate the stove again until you are certain the chimney and its lining have not been damaged OPERATION The door and ash drawer must be kept closed when the unit is in operation to prevent fume s...

Страница 4: ...bearing capacity if existing construction doesn t meet load capacity suitable measures e g load distributing plate must be taken to achieve it DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYST...

Страница 5: ...tection in front of and to the sides of the door opening Serial No No De Seri To Start Stove Select fuel type mode PREMIUM PELLETS for superior quality pellet fuel REGULAR PELLETS for all grades of wo...

Страница 6: ...ble 1 M 55 FS Specifications Description Fuel type Residential Pellet Heater 6mm dia Pellets wood corn wheat barley Voltage Current Max Power 110 120 V 4 2 Amps 504 Watts Frequency Hopper Capacity Con...

Страница 7: ...is to be installed on a carpeted area a solid surface wood metal or approved hearth pad must be installed between the unit and the carpet 6 This unit uses large quantities of air for combustion outsid...

Страница 8: ...a location that is not too close to the unit but will effectively heat the desired area 2 Connect the Thermostat or Timer using a 2 x 18 gauge wire from the unit to the thermostat If the heat in the...

Страница 9: ...rmination locations Table 2 Use in conjunction with Figure 7 for allowable exterior vent termination locations Letter Minimum Clearance Description A 24 in 61 cm Above grass top of plants wood or any...

Страница 10: ...irtight homes and mobile homes When connecting to an outside fresh air source do not use plastic or combustible pipe A 3 minimum 76 mm ID inside diameter steel aluminum or copper pipe or ducting shoul...

Страница 11: ...heater to the floor using the four 4 holes in the pedestal Ensure the unit is electrically grounded to the chassis of your home permanently Do not install in a room people sleep in Outside fresh air i...

Страница 12: ...fastened with at least three 3 screws 1 Place the appliance 15 37 5 cm away from the wall If the stove will be installed a hearth pad set the unit on it 2 Locate the center of the exhaust pipe on the...

Страница 13: ...installations have 3 to 5 feet 91 to 152 cm of vertical pipe in the system to help naturally draft the unit in the event of extreme weather or a power outage Some horizontal through wall installations...

Страница 14: ...Vertical section of vent pipe Horizontal frame for thimble 90o elbow Concrete Wall Clean out tee Installation to use if there is a concrete or retaining wall in line with exhaust vent on pellet stove...

Страница 15: ...Installations section and then finish it by performing the following refer to Figure 16 1 Install a tee with clean out on the outside of the house 2 Install PL vent upward from the tee Make sure that...

Страница 16: ...o when the pellet vent is installed vertically it will meet the minimum clearance from a combustible wall stated by the vent manufacturer 2 Install the tee with clean out 3 Install the pellet vent upw...

Страница 17: ...chimney If holes already exist fresh air intake can be taken through back of the fireplace or through the ash dump Installation Hearth Mount Installation Figure 18 Hearth Mount Side View Figure 19 He...

Страница 18: ...etting The reading can be taken from the hole located on the Unit s lower left Pedestal Side Note The slider screw is tightened at the factory to holding the slider fully open DO NOT ADJUST If after l...

Страница 19: ...or If the 3 light is flashing unit may be out of fuel Check the Door and Ash Pan door THEY MUST BE CLOSED TIGHT See section 8 The Fuel will not light Check the fuse on the circuit board If the unit st...

Страница 20: ...the ON OFF button 5 Unit is on but auger motor does not turn at all Check the line fuse to see if it has blown Check the Door and Ash Pan door THEY MUST BE CLOSED TIGHT If the Auger gear box does not...

Страница 21: ...eaves fresh unburned fuel in the burn pot liner the fire is going out before the stove shuts off Trim the combustion air down to decrease the magnahelic pressure Turn the Heat Level up slightly poor q...

Страница 22: ...e Purple White Convection Blower Agitator Motor Grey Grey Orange Orange White Grey Grey White Blue Yellow Auger Motor White Yellow Vacuum Switch Connect Thermostat Here Brown Brown Blue Purple Yellow...

Страница 23: ...Coupler 50 1697 6 Convection Blower 80mm 50 2064 7 Enviro Gel Decal 50 322 8 Auger With Paddles 50 1161 9 Ignitor Coil Type 400 Watt 50 1691 10 Auger Stops Clear Rubber 50 1559 11 Auger Plate And Bush...

Страница 24: ...nge Set of 2 50 2047 39 Exhaust Starter Tube Including Gasket 50 2043 40 Auger Tube Cover 50 1410 41 Hopper Lid Including Hinge 50 2037 42 Firebox Top 50 2040 43 Agitator Drive Bracket 50 2038 44 Cast...

Страница 25: ...25 Parts Diagram Components 27 1 2 3 4 5 6 7 8 9 10 12 13 11 14 15 16 17 18 19 22 21 20 25 24 23 26...

Страница 26: ...Parts Diagram Steel 26 55 56 57 58 34 35 47 40 33 32 31 30 29 28 54 51 52 53 49 50 48 46 44 41 45 43 42 39 36 37 38...

Страница 27: ...estrictions and exclusions apply to this warranty Limited Two 2 Year Warranty Under this warranty Sherwood Industries Ltd covers Ignitor Auger Motor Circuit Board Timers Temp Sensors Blowers Vacuum Sw...

Страница 28: ...ify the Limited Warranty on this stove If unsure as to the extent of this Limited Warranty contact your authorized Enviro dealer before installation 10 Sherwood Industries Ltd will not be responsible...

Страница 29: ...vered per our warranty service fee reimbursement schedule Labour rates are set per component and as such total labour costs may not be covered 27 Sherwood Industries Ltd is not liable for freight or l...

Страница 30: ...AL NUMBER ___________________________ DATE OF PURCHASE _____________ dd mm yyyy DATE OF INSTALLATION ___________ dd mm yyyy MAGNEHELIC AT INSTALL ___________________ INSTALLER S SIGNATURE ____________...

Отзывы: