21
Scenario #5
p
roblem
: p
iloT
liGhTs
,
sTops
sparkinG
,
and
piloT
remains
liT
. b
Urner
will
noT
liGhT
Possible Causes:
1� Faulty module�
2� Faulty valve�
*Note*
• Disconnect power to the system prior to disconnecting any components by switch the ON/OFF/
REMOTE module switch to the OFF position�
• It is not recommended to operate the ignition control module with disconnected wire connec-
tions� A short could cause permanent damage�
• Applying a false flame to the pilot sensor (i�e� lighter etc�) will cause the module to go into lock-
out mode� This is due to a safety feature�
Volts DC
1.6V to open valve
0.3V to keep valve open
Black
probe to body of
valve.
Red
probe to green wire
connected to valve. Pull wire
slightly away from connector
to touch connector
Check the voltage to the burner solenoid by connecting a multi-meter to the valve as shown in Fig-
ure 25 below� This test should be performed during the lighting sequence�
Figure 25: Dexen Valve - Burner Solenoid Valve
1. f
aUlTy
m
odUle
(b
Urner
s
olenoid
)