monitor
intercom
setup
exit
Outdoor Tone -- 01
Intercom Tone -- 05
Monitor Time -- 1min
Advanced Set...
Auto Record -- OFF
Exit
0
* * *
Password:
Slave Addr Set -- 0
Guard Unit Set -- 0
Date/Time Set...
Other Settings...
Information...
Exit
Hardware ver 0302
Software ver 0168
Voltage 22.4V
Manufacture 00.0T
Restore to default
Exit
Unlock Time 1
Unlock Mode 0
Exit
1. Press
setup
setup item
on main menu page.
2. Select Advanced Set...
password is required.
4. Select Information...
5. Press UNLOCK button
and hold for 2s.
6. Set unlock mode to
0 or 1.
3. The default password is
2008.
4.3 Electromagnetic Lock Connection
Note:
1. Only applicable to the power off to unlock type of electronic locks.
2. The door lock is limited to 12V, and holding current must be less than 250mA.
3. The door lock control is not timed from Exit Button(EB).
4. The Unlock Mode Parameter of Monitor must be set to 1 (by default).
4.3.1 Door Lock Controlled by Internal Power
Connect one lock
Jumper position in 1-2
1 2 3
EB
*
LOCK
BUS
PL
S1+ S2+ S-
Normally closed
Connect two lock
Jumper position in 1-2
EB
*
LOCK
LOCK
2
nd
1
ST
2
nd
EB
*
1
ST
1 2 3
BUS
PL S1+ S2+ S-
Note:
1. The external power supply must be used according to the lock.
2. The inside relay contact is restricted to AC or DC 24V/3A.
3. The jumper must be taken off before connecting.
4. Setup the Unlock Mode of Monitor for different lock types.
• Power-on-to-unlock type:Unlock Mode=0 (by default)
• Power-off-to-unlock type:Unlock Mode=1
4.3.2 Door Lock Controlled by Dry Contact
Connect two lock
Take off the Jumper
1 2 3
BUS
PL S1+ S2+ S-
LOCK
LOCK
POWER
SUPPLY
LOCK
BUS
PL
S1+ S2+ S-
POWER
SUPPLY
Connect one lock
Take off the Jumper
1 2 3
-7-
-6-
4.3.3 Unlock parameter setting(set in monitor)
Note:
1. Must connect DT596 correctly before setting.
2. The parameter will be saved in DT596 automatically,so you only need to set on one monitor.
3. The above cutline is fit for T107 series monitors only,for T753,T863 series monitors,please refer to the