Using the Terminal Configurator
A-8
[bridge]
Bridge provides variables that are common to all radios. Bridge affects the behavior of
radios.
AP refresh period. Periodically an Ethernet Adapter pings an Access Point.
The AP Refresh Period is the time, in units of seconds, between pings. The
default for this value is 60 (which should be left at this default). If this default
is changed, there is a chance that the Access Point will not find the Ethernet
Adapter unit on the network.
RS-232 port (uart0)
[hardware]
RS-232 serial UART configurations found on all UARTS.
•
baud. This selects the data transfer rate of the RS-232 serial port. The baud
rate can be anywhere between 112.5 and 115,200 bps. All standard rates (300,
1200, 2400, 9600, 19200, 38400, 57600, and 115200) are clocked precisely,
but values in between will be rounded to the closest possible hardware setting.
•
data bits. In a UART character frame, this selects the number of bits that are
used to transmit data. Possible values are 7 and 8.
•
parity. This sets the parity used in the UART character frame to check for
correct data transmission. Options are none, odd, and even.
•
stop bits. Selecting the number of bits used to represent an end of character
bit in the UART frame. The value can be 1 or 2.
Having this refresh period active will not effect the performance of the
Ethernet Adapter.
Closest possible hardware setting does not mean that the value will be
rounded to one of the standard rates. The Ethernet Adapter’s UART is fully
capable of operating at non-standard speeds. The resolution of possible
baud rates is smaller at lower baud rates than at higher baud rates.
NOTE
NOTE