5. Alarms
Alarms on Ensy AHU units
Critical alarms. Red flashing lights in the control panel
Alarm
Possible causes
Description of what
will happend
Reset of alarm
Motor
protection
Supply
Absence of signal from
the fan
EV and RO is
turnined off.
TV and AV turns off
after 1 min
Fan turns «
OFF
» and then back
to «
NORM
»
Motor
protection
Extract
Sensor
AT
open
The sensor is broken.
All functions are
deactivated and the
unit will stop
Automatic reset after
replacement
Sensor
OET
open
Overheating
The temperature has
excceded 55°C
Heater (EV) turns off
Automatically when temperature
sinking to 25°C
(earlier 20°C)
Fire thermostat
Temperature over
thermostat excedeed
110°C.
All functions are
deactivated and the
unit will stop.
Manual reset of the fire
thermostat.
Low voltage
Voltage drops below
200 V
All functions are
deactivated.
Automatically after voltage rises
to 212 V
No connection from
control panel to the
master control board.
All functions are
deactivated.
Automatically when contact is
established again
Less critical alarms. Yellow flashing lights in the control panel
Alarm
Possible
causes
Description of what
will happend
Reset of alarm
Sensor
EAT
open
Short circuit or breach
of cable.
All functions are
deactivated
Automatic reset after
replacement
Sensor
AVK
open
Sensor
UTE
open
Frost alarm
Supply air from unit is
under 5°C
All functions are
deactivated
When temperature rises above
9°C
Filter change
The period of use for
the filters is expired
Replace the filters.
See user manual
4.3 Filter
how
to reset alarm