Message Shown on
Events and Inventory
Screens
Description
ModuleAdd
Description:
The Envoy has detected and is now associated to a new
microinverter.
No action is required.
Microinverter failed to
report
Recommended Action:
Ignore occasional instances of this event. Communication
usually recovers on the next reporting cycle.
If communications do not recover immediately, ensure that the Envoy is plugged in
very near the Switchboard. Also, if other devices are sharing the AC socket with
the Envoy, remove those devices from the AC socket to improve signal strength.
If the Enphase Envoy was recently relocated or if new devices or appliances were
added to the circuit, it is possible that the new situation is not suitable for power
line communication. The Envoy may need to be relocated to improve signal
strength and reduce interfering noise on the power lines.
To determine the quality of the Envoy’s location for communication, run a
Communications check.
Description:
The Envoy reporting this condition is unable to communicate with the
microinverters over the power lines.
If the condition persists
: See “Power Line Communication Troubleshooting” on
page 34, or contact your installer, or refer to the Troubleshooting Guide at
enphase.com/support
.
Microinverter grid
configuration failed after 5
attempts, retrying
Description:
The attempt to change the grid profile for the microinverters has
failed after five tries. The Envoy will continue to attempt to change the grid profile.
Recommended Action:
No action is required.
Microinverter grid
configuration failure cleared
after xx attempts
Description:
A failed attempt to change the grid profile for the microinverters has
cleared. The grid profile was successfully applied.
xx = number of attempts
Recommended Action:
No action is required.
ModSleep
Description:
The microinverter is off for the night.
Recommended Action:
No action is required.
No Grid Profile
Recommended Action:
Ask the installer set up select a grid profile for this
system.
Description:
The Envoy has not been set up with a grid profile for the
microinverters.
OverTemperature
Description:
The microinverter is too hot and is not producing power. This very
rare condition usually clears without intervention.
Recommended Action:
No action is required unless the condition persists. If it
persists, contact Enphase Energy customer support.
PwrGenOffByCmd (Power
generation off by
command)
Description:
The microinverter is not producing power by user command. This
uncommon condition will occur only during isolated troubleshooting procedures by
Enphase personnel.
Recommended Action:
No action is required.
PowerOnReset
Description:
The microinverter has powered on after having DC disconnected.
Recommended Action:
No action is required.
RGM Error
Description:
The Enphase-compatible Revenue Grade Meter (RGM) has failed.
Recommended Action:
Contact your installer to arrange for installation of a
replacement meter.
RGM Power Quality
Warning
Description
: The Enphase-compatible Revenue Grade Meter (RGM) reports that
the AC voltage coming from the
grid
is either too low or too high as specified by
applicable regional standards. This is usually a temporary condition that will clear
when power quality from the
local grid
returns to normal.
Recommended Action
: No action is required unless the condition persists. If the
condition persists, contact your installer.