Installation and Operation Manual 

 Fan Coil Controller – EZstat 

EC-EZstat

Date: 9-2014 

Supersedes: NEW

Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation.

Page 30 of 36

  Table 8-1 

EZstat Input objects

Modulating fans

The fan starts a modulation fan on a call for either heating or cooling. The fan runs at the minimum dead band speed until 

the heating or cooling loop is above 50%, then the fan start to ramping up based on room temperature demand From 50% 

to 100% of the loop, the fan speed ramps to maximum speed. The minimum and maximum fan speeds are set from the 

user interface during system setup. 

Automatic fan control

A user with Password 1 can set the EZstat controlled fan to either run continuously or to start automatically on a call for 

cooling or heating.

Auto

—when Auto is selected, the fan runs at deadband, and when there is a call for cooling or heating, the fan will begin 

to modulate toward the maximum cooling or heating fan airflow. Fan will continue to run unless system mode is changed 

to Off mode on the user interface. 

Low, Medium, High

—for systems with three‑speed fans, the user has the choice of low, medium or high speed as the 

continuous running speed for the fan.

If the user selects one of these speeds on the user interface, this will override the auto functionality and Nailor 

sequences.  However, if the user accidentally overrides AUTO function, the AUTO FAN RESET (for ECM applications 

only) can prevent this from occurring, by Enabling the AUTO FAN RESET located in SYSTEM menu. The AUTO FAN 

RESET feature works together with LOCAL OVRD Time. To adjust default time of 60 mins, select LOCAL OVRD TIME. 

The control will reset back to Auto Mode, while ensuring the efficiency benefits of EON (variable speed) motor.

8  SYSTEM INTEGRATION

Topics in this section cover integrating EZstat controllers into a building automation network. These are advanced topics for 

control technicians and engineers.
The EZstat can function as a standalone controller or it can be connected to a BACnet MS/TP network. The topics in this section 

are reference material for control technicians or engineers that will be installing and setting up an EZstat that is connected to 

a network.
In addition to the information in this section, you will also need the following information.

• 

Detailed plans and drawings for the building automation system.

• 

Information about the facility LAN including routers, switches, and network firewalls.

• 

Application Note AN0404A, 

Planning BACnet Networks

.

  8.1  BACnet objects

The EZstat is a BACnet Application Specific Controller (ASC) that is composed of standard BACnet objects. This section 

lists the objects that are likely to be needed for monitoring with a standard BACnet operator workstation to verify system 

operation.

Changing  the  configuration  of  any  object  may  result  in  unpredictable  operation  of  the  EZstat  and  damage  to 

equipment that is under control of the EZstat.
Not all input objects are present in every model.

Input objects

The following BACnet input objects represent values at the physical inputs of the EZstat. Only inputs 1‑3 are available for 

external connections.

Input

Name

Description

Device Type Screen Display

AI1

REMOTE_SENSOR

Remote Room Sensor

KMC10K_Type_II

AI2

WATER_TEMP

Water Temperature

KMC10K_Type_III

AI3

DAT

Discharge  Air Temp

KMC10K_Type_III

AI4

LOCAL_SENSOR

Space Temp

KMC10K_Type_II

NOTE

NOTE

Содержание Fan Coil Controller EZstat

Страница 1: ...2014 Supersedes NEW Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation Page 1 of 36 www Engineered Comfort com Fan Coil C...

Страница 2: ...ADMIN PASSWORD 13 5 3 CHANGING THE ACTIVE SETPOINTS 13 5 4 SETTING THE OPERATING MODES 14 6 COMMISSIONING FUNCTIONS 15 6 1 CREATING AND OR CHANGING PASSWORDS 16 6 2 SETTING THE COMMISSIONING SETPOINTS...

Страница 3: ...EZstat combines the power of a space mounted equipment controller with the convenience of built in temperature sensors The EZstat controller includes a wide range of factory supplied programs for two...

Страница 4: ...omatically detected Inputsacceptindustry standard10 000 TypeII NailorPart H1 1989 orTypeIII NailorPart H1 0246andH1 1764B thermistors sensors Input overvoltage protection up to 24 VAC continuous 12 bi...

Страница 5: ...FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may...

Страница 6: ...ate 9 2014 Supersedes NEW Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation Page 6 of 36 3 4EZstatFeatures Power and Outp...

Страница 7: ...he day Exposed to drafts from windows diffusers or returns Exposed to air flow through connecting conduits or empty spaces behind walls Rough in preparation Complete rough in wiring at each location b...

Страница 8: ...ls The input includes the internal pull up resistor Follow the instructions supplied with the sensor for installation When a remote space temperature input is connected to the EZstat the remote temper...

Страница 9: ...outputs are configured for specific applications Depending on the configuration the EZstat outputs are designed for either 24 VAC or 0 10 VDC loads The outputs may represent analog or digital signals...

Страница 10: ...following diagram shows the connections for a modulating speed fan The fan start circuit must be a 24 VAC circuit Connect it to the FAN L output The speed control is a 0 10 VDC analog output Fig 4 5...

Страница 11: ...g 4 7 Connecting on off valve COM R B05 4 4 Connecting Power The EZstat requires an external 24 VAC power source Use the following guidelines when choosing and wiring transformers Use only a Class 2 t...

Страница 12: ...wing functions Back Returns to the previous menu Cncl Cancels current changes Done Push this button at any point while entering a value For example if you have entered the first two digits of a passwo...

Страница 13: ...2 respectively User functions may require a password consisting of four numbers Once either the User or Admin level password is entered the functions will remain unlocked for 60 seconds after the las...

Страница 14: ...the fan mode from the following options Auto Default Auto function is utilized to match EPIC ECM motor with this feature for optimum energy savings AUTO FAN RESET for ECM applications only by enabling...

Страница 15: ...automatically place the system in the override mode F 65 AUTO AUTO Enter Cncl LOCAL OVRD ON OFF Change the display units To temporarily change the display units to either Celsius or Fahrenheit press a...

Страница 16: ...lls up Password 2 in the program This is generally used by a controls technician to set up and commission the EZstat When set will lock user out from setpoints fan operation occupancy and heating and...

Страница 17: ...mum cooling setpoint that a user can select as the active setpoint MAX HEATING The maximum heating setpoint that a user can select as the active setpoint DIFFERENTIAL The minimum value between the coo...

Страница 18: ...rocedure Steps Display Starting Display 1 Start at the temperature display 2 Enter Password 2 The display changes to the MAIN menu display F 70 AUTO AUTO Enter SECURITY ADMIN LEVEL 0 0 0 0 Change the...

Страница 19: ...s between local standard time and Universal Time Coordinated The value of the property ranges from 780 to 780 seconds The time zones to the west of the zero degree meridian are positive values those t...

Страница 20: ...of the week at one time WEEKDAYS Sets the schedule for Monday to Friday Saturday and Sunday are not changed WEEKEND Sets the schedule for Saturday and Sunday Monday to Friday remain unchanged INDIVIDU...

Страница 21: ...e will override the values of the weekly schedule DATE RANGE Enter a range of dates on which the values and times listed in the holiday schedule will override the values of the weekly schedule WEEK N...

Страница 22: ...tpoint as the active setpoint Set the fan delay From the SYSTEM menu choose FAN DELAY OFF to set the time the system fan will continue to run after the last heat ing or cooling stage is turned off Set...

Страница 23: ...8 337 1 92 526 4 33 705 6 74 873 9 15 343 1 99 531 4 40 710 6 81 878 9 22 349 2 06 536 4 47 715 6 88 883 9 29 355 2 13 542 4 54 720 6 95 888 9 36 361 2 20 547 4 61 725 7 02 893 9 43 367 2 27 552 4 68...

Страница 24: ...two pipe only From the SYSTEM menu choose Stage 1 fan Select the fan for Stage 1 Enter STAGE 1 FAN 50 Set Stage 2 Fan two pipe only From the SYSTEM menu choose Stage 2 fan Select the fan for Stage 2...

Страница 25: ...ABLED Procedure Steps Display Starting Display 1 Start at the temperature display 2 Enter Password 2 The display changes to the MAIN menu display F 70 AUTO AUTO Enter SECURITY ADMIN LEVEL 0 0 0 0 Choo...

Страница 26: ...oves the password The EZstat is supplied without passwords 1 From the PASSWORD1 or PASSWORD2 menu either the or button to change the first digit of the password 2 Press the Enter button to select the...

Страница 27: ...etpoint Limits The programming in the EZstat will limit the setpoint entry so that no heating setpoint is set higher than its corresponding cooling setpoint If a user is adjusting a setpoint and it fa...

Страница 28: ...ng applications The EZstat is configured for a Type III thermistor sensor or Nailor Part H1 1764B to monitor water temperature The water temperature can be monitored as an analog input and is also sto...

Страница 29: ...n be added to two pipe systems Typically this heat is a duct or baseboard resistance heater controlled by a relay When the supply water type is chilled water and there is a call for heat the EZstat co...

Страница 30: ...er with LOCAL OVRD Time To adjust default time of 60 mins select LOCAL OVRD TIME The control will reset back to Auto Mode while ensuring the efficiency benefits of EON variable speed motor 8 SYSTEM IN...

Страница 31: ...Fan Speed Control 0 100 0 10 V B01 LOW Fan Low Speed Unknown B02 MEDIUM Fan Medium Speed Unknown B03 HIGH Fan High Speed Unknown B04 BINARY_COOLING Cooling Valve Unknown B05 BINARY_HEATING Heating Val...

Страница 32: ...for the EZstat applications All of the setpoints are available from the user interface Value object Name Description AV3 ACT_COOL_STPT Active Cooling Setpoint AV4 ACT_HEAT_STPT Active Heating Setpoin...

Страница 33: ...6 DAT_ENABLE DAT Enable BV7 DAT_SENSOR DAT Sensor Present BV9 FAN_NEED Call for Fan BV10 COOL_HEAT_NEED Cooling or Heating needed BV11 SPEED_UP Speed up Timers x15 BV13 OCCUPIED_FAN Fan On During Occu...

Страница 34: ...no more than 128 addressable BACnet devices to one MS TP network The devices can be any mix of EZstat controllers other BACnet controllers or BACnet routers To prevent network traffic bottlenecks lim...

Страница 35: ...or specification without notice or obligation Page 35 of 36 The controllers or devices on the physical ends of the MS TP wiring segment must have end of line EOL termination installed for proper netwo...

Страница 36: ...oil Controller EZstat EC EZstat Date 9 2014 Supersedes NEW Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation Page 36 of 3...

Отзывы: