Procedure
Steps
Display
Starting Display
1.
Start at the temperature display.
2.
Enter Password 2. The display changes to the MAIN menu display.
F
°
70
AUTO
AUTO
Enter
SECURITY
ADMIN LEVEL
0
0 0 0
Select the
SCHEDULE
menu.
1. From the MAIN menu, press either the
or
button to
select SCHEDULE.
2. Press
Enter
. The SCHEDULE menu opens.
3. Choose SET CLOCK and then press
Enter
. The SET Clock menu
opens.
Choose a clock
function to set.
Choose one of the features in the SET CLOCK menu to change the
date, time, or Daylight Saving Time (DST) setting.
•
DATE—The current calendar date.
•
TIME—Time is set according to a 12‑hour clock.
•
UTC OFFSET—Enter the time offset, in minutes, between local
standard time and Universal Time Coordinated. The value of the
property ranges from ‑780 to +780 seconds. The time zones to
the west of the zero degree meridian are positive values; those
to the east are negative values. The value of the UTC Offset
property is subtracted from the UTC received in a UTC Time
Synchronization service request to calculate the correct local
standard time.
•
DST ENABLE—Set to TRUE to enable Daylight
•
Saving Time and FALSE to use standard time year around.
•
DST AUTO—When set to TRUE, the EZstat automatically
calculates the start and end dates from relative dates. For
example, set DST START to the first Sunday in March instead of a
calendar date.
•
DST START and DST END—Enter the dates and time to begin
observing DST. If DST AUTO is set to TRUE the dates are relative;
if set to FALSE the date is a calendar date.
6.4 Set the time and date
Setting the time and date requires entering Password 2.
If the EZstat is connected to a BACnet network that includes a time service master, the time and date are automatically
set to the network time and date.
Set the time and date
NOTE