OPERATING MANUAL FOR AUTOMATIC VOLTAGE REGULATOR

MODEL NO : EVC300i

1. INTRODUCTION

2. ENVIRONMENTAL

3. TECHNOLOGY SPECIFICATION

The EVC300i Voltage Regulator is thyristor base to control the DC exciter field power of conventional
50 or 60 Hz brushless generators. The AVR circuitry includes under speed and over load protection
features. Excitation power is derived directly from the generator terminals.

-30 to 80°C (-22 to 176 F)

-40 to 80°C (-40 to 176 F)

Less than 2800 meter

<90%

2.1. Operating temperature:
2.2. Storage temperature:
2.3. ALTITUDE:
2.4. RELATIVE HUMIDITY:

Sensing Input

Power Input

Voltage Adjust Range

Field Resistance

Voltage Regulation

Output Voltage

Output Current

Terminal V - V

for 220 Vac

Terminal V - V

for 400 Vac

Voltage: 180 to 250 Vac
Frequency: 50 Hz or 60 Hz

180 - 300 Vac, 300 - 520 Vac

< 1%

Maximum 90 Vdc @ 240 Vac

Maximum continuous: 6.3 A @ 240 Vac
10 second forcing: 10 A @ 240 Vac

220

380

Recommend 9 - 24

±

Ω

Paralleling

Voltage Buildup

External Volts Adjustment

Thermal Drift

Analog Voltage Input

Current Compensation

Dimensions

Weight

Internal burden and adjustment for 0 to 10%
droop at 1 A, 0.8 PF, (from external CT)

4Vac, 30 Hz

At least

10% with 100k ohm 1 watt trimmer

0.05% per

C

change in AVR ambient

In : 1A Input
Not Less than 10 % @ P.F. = 0.8

122 mm L x 93 mm W x 38 mm H

300

10g

±

±5VDC, adjustable output voltage is no less than
2% for 1VDC (i.e. for ±5VDC it come out to be
±10%)

±

EVC300i

Generator Automatic Voltage Regulator

Operation Manual

Page 1 of 7

Updated on 02 Feb2015

Содержание EVC300i

Страница 1: ...ulation Output Voltage Output Current Terminal V V for 220 Vac Terminal V V for 400 Vac Voltage 180 to 250 Vac Frequency 50 Hz or 60 Hz 180 300 Vac 300 520 Vac 1 Maximum 90 Vdc 240 Vac Maximum continuous 6 3 A 240 Vac 10 second forcing 10 A 240 Vac 220 380 Recommend 9 24 Ω Paralleling Voltage Buildup External Volts Adjustment Thermal Drift Analog Voltage Input Current Compensation Dimensions Weigh...

Страница 2: ...EVC300i Figure 1 Outline Drawing OPERATING MANUAL FOR AUTOMATIC VOLTAGE REGULATOR MODEL NO EVC300i Page 2 of 7 4 MECHANICAL SPECIFICATION DRAWING S 1 ON Increase in Response Time OFF Response as per STAB pot Set SW ON 60 HZ OFF 50 HZ 2 122 mm 93 mm 108 mm 80 mm S1 S2 VR VR V380 N V220 V F F 2 1 A A 2 X 4 4 mm 1 2 O L LED O L POT TRIM UFRO LED FUSE 6 3 Amps 38 mm U U U F V V380 VR1 S1 S2 VR2 V220 N...

Страница 3: ...maximum and can be connected to A A terminals for at least 10 variation in terminal voltage When 60Hz operation AVR response time needs to be reduced For that turn ON Switch1 so that extra fixed response time is now added with STAB POT setting such that no over or under shoot of voltage occurs during loading unloading of generator at 60Hz When 50Hz operation no need to decrease response time as ST...

Страница 4: ...ions For 50 Hz applications the frequency roll off is factory preset to between 46 8 and 47 2 Hz To reset the frequency roll off proceed as follows a Adjust the prime mover RPM to the desired frequency compensation corner frequency roll off point b If UFRO LED is ON adjust the back panel trimmer anticlock wise to just OFF the LED If UFRO LED is OFF then adjust UFRO trimmer clockwise to turn ON LED...

Страница 5: ... S1 S2 VR VR V380 N V220 V F F 2 1 Exciter Field Armature Stator Wire 100K 1W 5 Vdc Analogue Input CT 1A 1 2 W N V U IN A A FUSE 6 3 Amps O L LED O L POT TRIM ON SW ON 60 HZ OFF 50 HZ 2 SW1 ON Increase in Response Time OFF Response as per STAB pot Set Note All doted lines are optional connections Updated on 02 Feb2015 UFRO LED ...

Страница 6: ...7 S1 S2 VR VR V380 N V220 V F F 2 1 A A Exciter Field Armature Stator Wire 5 Vdc Analogue Input W V U CT 1A IN 100K 1W SW ON 60 HZ OFF 50 HZ 2 SW1 ON Increase in Response Time OFF Response as per STAB pot Set FUSE 6 3 Amps O L LED O L POT TRIM ON 1 2 Note All doted lines are optional connections Updated on 02 Feb2015 UFRO LED ...

Страница 7: ...C VOLTAGE REGULATOR MODEL NO EVC300i Page 7 of 7 S1 S2 VR VR V380 N V220 V F F 2 1 220V100W LAMP 230Vac 50Hz A A FUSE 6 3 Amps O L LED O L POT TRIM SW ON 60 HZ OFF 50 HZ 2 SW1 ON Increase in Response Time OFF Response as per STAB pot Set ON 1 2 Updated on 02 Feb2015 ...

Отзывы: