OPERATING MANUAL FOR AUTOMATIC VOLTAGE REGULATOR

MODEL NO : EVC300i

Page 4 of 7

value (which is set using O/L POT), internal timer
starts and if overloading condition continues for 20
seconds then after 20 seconds AVR cuts off  field
voltage and generator voltage is shut off. O/L LED
continues to light indicating O/L Trip. Adjustable from
0.1Amp to 7Amp DC. When O/L POT is fully
anticlockwise is minimum setting and fully clockwise
is maximum. Internal delay timer is fixed and delay
time is 20 seconds ±1%

To operationally test any EVC300i, refer to Figure 5
and perform the following steps:

a. Connect the voltage regulator as shown in Figure
5 and apply 230 Vac 50 Hz.
b. Adjust the rear panel

trimmer fully

clockwise (CW).
RESULT: Observe that the lamp lights up full.
c. Adjust the rear panel

trimmer fully counter-

clockwise (CCW).
RESULT: Observe that the lamp is not lit.
d. Adjust the rear panel

trimmer until the

lamp just goes out.
Regulator operation is satisfactory if the above
results are obtained. Stability, however must be
tested with the generator and regulator operating.

OPERATIONAL TEST

VOLT

VOLT

VOLT

From this position, rotate STAB POT anti-
clockwise direction till voltage is stable. Load the
generator and check for stable voltage and if not
then rotate more towards anticlockwise till voltage
is stable.

The EVC300i under frequency adjust is factory
preset to cause voltage drop in the generator
line voltage when the frequency is between 56.8
and  57.2 Hz for 60 Hz applications. For 50 Hz
applications, the frequency roll-off is factory preset
to between 46.8 and 47.2 Hz.
To reset the frequency roll-off, proceed as follows:
a. Adjust the prime mover RPM to the desired
frequency compensation (corner frequency roll-off)
point.
b. If UFRO LED is ON adjust the back panel

trimmer anticlock wise to just OFF the LED

If UFRO LED is OFF then adjust UFRO trimmer
clockwise to turn ON LED and then anticlockwise
to just turn it OFF.
c. Bring the prime mover up to rated speed. The
output voltage should return to set level.

Generator intended for parallel are fitted with a
quadrature droop CT which provides a power
factor dependent signal for the AVR. The CT
connected to

and

of AVR. CT with

secondary N:1A is required to provide minimum
10% droop at 0.8 PF. Percentage of droop
required can be adjusted using DROOP POT in
the range of 0 to 10%. Fully anticlockwise is 0%
and fully clockwise is maximum as per CT current
and load power factory. Factory set is 0% so that
mostly during solo operation there is no droop in
terminal voltage.

Trim Pot is used to decrease the effect of analog
input voltage on generator output voltage. When
set fully anticlockwise, there is no variation in
generator voltage on application of DC voltage on
A+ & A- Fully clockwise has maximum effect. Thus
using this POT we can get intermediate
percentage variation of the full scale - 10% at
± 5VDC.

.

Over load protection provides protection to
generator against overloading. It is based on field
current when field current increase above set

3. UFRO: Frequency Roll-Off Adjustment.

UFRO

4. DROOP: Droop Adjustment.

S1

S2

5. TRIM: Analog  Voltage Input Adjustment.

6. O/L : Over Load Protection

Updated on 02 Feb2015

Содержание EVC300i

Страница 1: ...ulation Output Voltage Output Current Terminal V V for 220 Vac Terminal V V for 400 Vac Voltage 180 to 250 Vac Frequency 50 Hz or 60 Hz 180 300 Vac 300 520 Vac 1 Maximum 90 Vdc 240 Vac Maximum continuous 6 3 A 240 Vac 10 second forcing 10 A 240 Vac 220 380 Recommend 9 24 Ω Paralleling Voltage Buildup External Volts Adjustment Thermal Drift Analog Voltage Input Current Compensation Dimensions Weigh...

Страница 2: ...EVC300i Figure 1 Outline Drawing OPERATING MANUAL FOR AUTOMATIC VOLTAGE REGULATOR MODEL NO EVC300i Page 2 of 7 4 MECHANICAL SPECIFICATION DRAWING S 1 ON Increase in Response Time OFF Response as per STAB pot Set SW ON 60 HZ OFF 50 HZ 2 122 mm 93 mm 108 mm 80 mm S1 S2 VR VR V380 N V220 V F F 2 1 A A 2 X 4 4 mm 1 2 O L LED O L POT TRIM UFRO LED FUSE 6 3 Amps 38 mm U U U F V V380 VR1 S1 S2 VR2 V220 N...

Страница 3: ...maximum and can be connected to A A terminals for at least 10 variation in terminal voltage When 60Hz operation AVR response time needs to be reduced For that turn ON Switch1 so that extra fixed response time is now added with STAB POT setting such that no over or under shoot of voltage occurs during loading unloading of generator at 60Hz When 50Hz operation no need to decrease response time as ST...

Страница 4: ...ions For 50 Hz applications the frequency roll off is factory preset to between 46 8 and 47 2 Hz To reset the frequency roll off proceed as follows a Adjust the prime mover RPM to the desired frequency compensation corner frequency roll off point b If UFRO LED is ON adjust the back panel trimmer anticlock wise to just OFF the LED If UFRO LED is OFF then adjust UFRO trimmer clockwise to turn ON LED...

Страница 5: ... S1 S2 VR VR V380 N V220 V F F 2 1 Exciter Field Armature Stator Wire 100K 1W 5 Vdc Analogue Input CT 1A 1 2 W N V U IN A A FUSE 6 3 Amps O L LED O L POT TRIM ON SW ON 60 HZ OFF 50 HZ 2 SW1 ON Increase in Response Time OFF Response as per STAB pot Set Note All doted lines are optional connections Updated on 02 Feb2015 UFRO LED ...

Страница 6: ...7 S1 S2 VR VR V380 N V220 V F F 2 1 A A Exciter Field Armature Stator Wire 5 Vdc Analogue Input W V U CT 1A IN 100K 1W SW ON 60 HZ OFF 50 HZ 2 SW1 ON Increase in Response Time OFF Response as per STAB pot Set FUSE 6 3 Amps O L LED O L POT TRIM ON 1 2 Note All doted lines are optional connections Updated on 02 Feb2015 UFRO LED ...

Страница 7: ...C VOLTAGE REGULATOR MODEL NO EVC300i Page 7 of 7 S1 S2 VR VR V380 N V220 V F F 2 1 220V100W LAMP 230Vac 50Hz A A FUSE 6 3 Amps O L LED O L POT TRIM SW ON 60 HZ OFF 50 HZ 2 SW1 ON Increase in Response Time OFF Response as per STAB pot Set ON 1 2 Updated on 02 Feb2015 ...

Отзывы: