OPERATING MANUAL FOR AUTOMATIC VOLTAGE REGULATOR

MODEL NO : EVC300i

AVR can be mounted directly on the  generator, switchgear or control panel that conforms to the
mounting specification.
All voltage readings are to be taken with an average-reading voltmeter. Meggers and high-potential test
equipment must not be used with AVR connected to generator. Use of such equipment could damage
the AVR.

5. WIRING

1. V - V

- V

: Sensing Input Voltage.

V

output voltage 220Vac

output voltage 400Vac

2. F+. F- : Excitation Output

3. Power Input:

For 400 Vac system

For 220 Vac system

4. S1 - S2:

220

380

Sensing Input is between

&

(220Vac) or

&

(400VAC). For 2 Phase sensing one

phase is connected to

terminal of AVR and

second phase is connected to

or

as

explained below:-
- For generator

, connect

sensing phase to terminal

.

- For generator

, connect

sensing phase to terminal

.

The sensing should be connected

Line to Line

from generator output. Refer Figure 3 & 4.

.

Connect the brushless exciter field to terminals F+
and F-. Be sure to observe polarity.

AVR power input is between N

& V.

N is connected to

Neutral of generator & V  to V Phase of generator.

, N is connected to U Phase

& V to V Phase of generator. Refer to Figure
3 & 4.

Current compensation input.

Current Transformer(CT) secondary current = 1A,
0.8 PF.

V

V

V

V

V

V

V

V

220

380

220

380

220

380

External Voltage Adjustment.

If an external voltage adjust control is being used,
connect a 100 K / 1 watt potentiometer to
terminals

and

as shown in Figure 3 & 4.

If not in use then let VR1 & VR2 is left open.

: Analog Voltage Input.

Fully isolated analog voltage from PF controller or
any other type of Digital (PLC) controller can be
injected into AVR for variation of generator output
voltage. Analog voltage range is ± 5VDC maximum
and can be connected to A+ & A- terminals for
at least 10 % variation in terminal voltage.

When 60Hz operation, AVR response

time needs to be reduced. For that turn ON Switch1
so that extra fixed response time is now added with
STAB POT setting such that no over or under shoot
of voltage occurs during loading-unloading of
generator at 60Hz.

: When 50Hz operation, no need to

decrease response time as STAB POT setting is
proper for optimum stability of generator with
minimum over-under shoot of Voltage during
loading - unloading of generator.

For 60 Hz operation of UFRO

For 50 Hz operation of UFRO

5. VR1 - VR2:

VR1

VR2

6. A+ & A-

7. DIP SWITCH:
a) SW1 - ON:

SW1 - OFF

b) SW2 - ON:

SW2 - OFF:

6. ADJUSTMENT

All trimmer build in back of the AVR board, except
the

and

Trimmer. The trimmers include

as shown in

Figure 2. For

Trimmer and

Trimmer refer

to Figure 1

The generator output can be altered by
adjustment of the

trimmer on the AVR board,

or by the external trimmer (100K ohm 1W) if fitted.

a) The terminals

and

must be left

unconnected if no hand trimmer is required.

O/L

TRIM

DROOP, UFRO, STAB and VOLT

O/L

TRIM

1. VOLT: Voltage Adjustment.

VOLT

Vset is factory set for 400 Vac , If Vset is
disturbed and set value is not known then
proceed as below :

VR1

VR2

.

Connect a voltmeter to generator output voltage

terminals.
d) Start the generator set and run on no load at
nominal frequency 50 - 53 Hz or 60 - 63 Hz.
e) If the red Led is illuminated, refer to the under
frequency roll off adjustment.
f)  Carefully turn volt trimmer clockwise until rated
voltage is reached.

Stability Pot is factory set for optimum performance
& is advisable not to disturb. But if required then
with the generator in ON Condition, rotate STAB
POT clockwise direction till voltage start oscillating
fast.

b) Before starting the generator, please turn the

trimmer on the AVR board fully anti-

clockwise.
c)

VOLT

2. STAB: Stability Adjustment.

Page 3 of 7

Updated on 02 Feb2015

Содержание EVC300i

Страница 1: ...ulation Output Voltage Output Current Terminal V V for 220 Vac Terminal V V for 400 Vac Voltage 180 to 250 Vac Frequency 50 Hz or 60 Hz 180 300 Vac 300 520 Vac 1 Maximum 90 Vdc 240 Vac Maximum continuous 6 3 A 240 Vac 10 second forcing 10 A 240 Vac 220 380 Recommend 9 24 Ω Paralleling Voltage Buildup External Volts Adjustment Thermal Drift Analog Voltage Input Current Compensation Dimensions Weigh...

Страница 2: ...EVC300i Figure 1 Outline Drawing OPERATING MANUAL FOR AUTOMATIC VOLTAGE REGULATOR MODEL NO EVC300i Page 2 of 7 4 MECHANICAL SPECIFICATION DRAWING S 1 ON Increase in Response Time OFF Response as per STAB pot Set SW ON 60 HZ OFF 50 HZ 2 122 mm 93 mm 108 mm 80 mm S1 S2 VR VR V380 N V220 V F F 2 1 A A 2 X 4 4 mm 1 2 O L LED O L POT TRIM UFRO LED FUSE 6 3 Amps 38 mm U U U F V V380 VR1 S1 S2 VR2 V220 N...

Страница 3: ...maximum and can be connected to A A terminals for at least 10 variation in terminal voltage When 60Hz operation AVR response time needs to be reduced For that turn ON Switch1 so that extra fixed response time is now added with STAB POT setting such that no over or under shoot of voltage occurs during loading unloading of generator at 60Hz When 50Hz operation no need to decrease response time as ST...

Страница 4: ...ions For 50 Hz applications the frequency roll off is factory preset to between 46 8 and 47 2 Hz To reset the frequency roll off proceed as follows a Adjust the prime mover RPM to the desired frequency compensation corner frequency roll off point b If UFRO LED is ON adjust the back panel trimmer anticlock wise to just OFF the LED If UFRO LED is OFF then adjust UFRO trimmer clockwise to turn ON LED...

Страница 5: ... S1 S2 VR VR V380 N V220 V F F 2 1 Exciter Field Armature Stator Wire 100K 1W 5 Vdc Analogue Input CT 1A 1 2 W N V U IN A A FUSE 6 3 Amps O L LED O L POT TRIM ON SW ON 60 HZ OFF 50 HZ 2 SW1 ON Increase in Response Time OFF Response as per STAB pot Set Note All doted lines are optional connections Updated on 02 Feb2015 UFRO LED ...

Страница 6: ...7 S1 S2 VR VR V380 N V220 V F F 2 1 A A Exciter Field Armature Stator Wire 5 Vdc Analogue Input W V U CT 1A IN 100K 1W SW ON 60 HZ OFF 50 HZ 2 SW1 ON Increase in Response Time OFF Response as per STAB pot Set FUSE 6 3 Amps O L LED O L POT TRIM ON 1 2 Note All doted lines are optional connections Updated on 02 Feb2015 UFRO LED ...

Страница 7: ...C VOLTAGE REGULATOR MODEL NO EVC300i Page 7 of 7 S1 S2 VR VR V380 N V220 V F F 2 1 220V100W LAMP 230Vac 50Hz A A FUSE 6 3 Amps O L LED O L POT TRIM SW ON 60 HZ OFF 50 HZ 2 SW1 ON Increase in Response Time OFF Response as per STAB pot Set ON 1 2 Updated on 02 Feb2015 ...

Отзывы: