ENFORCER Delayed Egress Timer 

 

10

 

                                                        

SECO-LARM U.S.A., Inc.

 

 

 

 

Sample Application – Installation in a Building

 

 

In this application, the SA-025EQ is used to delay exit from a building. 

 

Relock mode set to standard mode. 

 

Pre-delay timer set to 15 seconds. 

 

Power-up mode set to automatic relock (DIP Switch 1 OFF). 

 

Nuisance delay set to 0 seconds (DIP Switch 2 and 3 OFF). 

 

Lock status jumper ON. 

 

Security mode jumper OFF. 

 

Local alarm output type jumper ON. 

1.

 

A N.C. magnetic contact mounted on a door is connected to the lock status input so the SA-025EQ 
knows if the door is opened or closed. 

2.

 

A push-to-exit bar is connected to the initiate input. This device will be the primary means of egress. 

3.

 

A spring-loaded switch is connected to the reset input. This device will manually reset  
the lock. 

4.

 

A spring-loaded switch is connected to the pre-delay bypass input. This will allow any authorized 
user immediate access to the protected premises. 

5.

 

An alarm buzzer is connected to the local alarm output to indicate when the SA-025EQ is in the 
process of unlocking a door. The alarm buzzer will remain active for 5 seconds after the door is 
unlocked. 

6.

 

An electromagnetic lock is connected to the lock relay output. 

7.

 

A strobe light is connected to the remote alarm relay output. This device will signal at a remote 
location whenever the remote alarm relay output is triggered. 

8.

 

The bypass input and free egress input are not used. Jumpers are placed between the bypass input, 
free egress input, and positive power input terminal.  

Magnetic contact 

Push-to-exit bar 

Spring-loaded switch 

Electromagnetic lock 

Alarm buzzer 

Strobe light 

Power 
supply 

Содержание ENFORCER SA-025EQ

Страница 1: ...lay outputs for lock relay and remote alarm Transistor ground output for local alarm outputs Auto or programmed relocking after power loss IMPORTANT Users and installers of this product are responsibl...

Страница 2: ...put Form C 10A 24VDC Local alarm output transistor ground 500mA 12VDC Door status input Status LEDs show relay status Bypass input immediately releases locks Free egress input allows easy egress durin...

Страница 3: ...er see pg 6 Post delay timer potentiometer see pg 6 Terminal block see pg 4 LED 1 Blue If ON the SA 025EQ is being powered see pg 9 LED 2 Red If ON the lock relay is energized see pg 8 LED 3 Red If ON...

Страница 4: ...holes located on the side of the unit to a mounting surface Normally energized Screen print refers to energized state as normal Remote alarm relay output 10A 24VDC Form C Relay NO NC COM see pg 8 Loc...

Страница 5: ...relocked by a reset device connected to the Reset Input For information on connecting a reset device see pg 4 Wiring Diagram This reset device is often a momentary spring loaded key switch BOCA Mode T...

Страница 6: ...h at the bottom right of the circuit board Power Up Mode DIP Switch 1 There are two types of power up modes These modes determine the relocking status in case of a power loss Programmed Relock DIP Swi...

Страница 7: ...al alarm pulses during the pre delay gradually pulsing faster until the end of the pre delay time The local alarm will continue signaling steady 5 seconds after the lock has been released When set OFF...

Страница 8: ...e pg 7 LED 4 red is on when the local alarm output is active Lock Relay Output The SA 025EQ is equipped with a 10A 24VDC Form C dry relay output that can be used with a fail safe or fail secure lock T...

Страница 9: ...e bypass input is used to bypass the SA 025EQ and allow unrestricted entry and exit via the door When the bypass input is activated the lock will immediately release It will remain released until the...

Страница 10: ...ted to the reset input This device will manually reset the lock 4 A spring loaded switch is connected to the pre delay bypass input This will allow any authorized user immediate access to the protecte...

Страница 11: ...mon terminal is connected to a positive voltage and the normally closed terminal is connected to the SA 025EQ s initiate input 3 An audible indicator sounds during the pre delay time to alert the user...

Страница 12: ...rkmanship The sole obligation of SECO LARM and the purchaser s exclusive remedy shall be limited to replacement or repair only at SECO LARM s option In no event shall SECO LARM be liable for any speci...

Отзывы: