ENFORCER Delayed Egress Timer 

 

6

 

                                                        

SECO-LARM U.S.A., Inc.

 

 

 

 

Adjusting the Pre-Delay and Post-Delay: 

Pre-delay timer 
potentiometer 

Post-delay timer 
potentiometer 

The pre-delay and post-delay timers can be 
adjusted using the potentiometers located on 
the bottom left of the circuit board. 

 

Pre-Delay:

 The pre-delay timer can be  

adjusted from 1~30 seconds. This sets the 

delay time between when the initiate device is 
used and the lock is released. Once the initiate 

device is triggered, the process cannot be 
stopped unless the reset input is activated  
(1-second default). 

 

Post-Delay:

 The post-delay timer can be 

adjusted from 1~60 seconds. This sets how 
long the door remains unlocked in the timer 
mode (1-second default). 

Setting the Power-Up Mode and Nuisance Delay: 

The power-up mode and nuisance delay are 

set using the DIP switch at the bottom right 
of the circuit board. 

Power-Up Mode (DIP Switch 1)  

There are two types of power-up modes. These modes determine the relocking status in 
case of a power loss. 

Programmed Relock (DIP Switch 1 ON)

: In the event of a power loss, the lock will 

release. When power is restored, the lock will relock according to the programmed mode 
and relock time configuration. (See pg. 5, 

Relock Modes

.)

 

Automatic Relock (Default, DIP Switch 1 OFF)

: In the event of a power loss, the lock will 

release. When the power is restored, the lock will automatically relock. 

Nuisance Delay (DIP Switch 2 and 3)  

The nuisance delay determines how long the initiate device (such as a push-to-exit bar) must be 
activated before the pre-delay timer will start. The nuisance delay can be programmed  
from 0~3 seconds. 

NOTE:

 Nuisance delay requirements will vary depending on local laws and codes.  

0 Seconds (Default, DIP Switch 2 and 3 OFF)

  

1 Second (DIP Switch 2 ON and 3 OFF)

  

2 Seconds (DIP Switch 2 OFF and 3 ON)

  

3 Seconds (DIP Switch 2 ON and 3 ON)

  

DIP Switch 

Содержание ENFORCER SA-025EQ

Страница 1: ...lay outputs for lock relay and remote alarm Transistor ground output for local alarm outputs Auto or programmed relocking after power loss IMPORTANT Users and installers of this product are responsibl...

Страница 2: ...put Form C 10A 24VDC Local alarm output transistor ground 500mA 12VDC Door status input Status LEDs show relay status Bypass input immediately releases locks Free egress input allows easy egress durin...

Страница 3: ...er see pg 6 Post delay timer potentiometer see pg 6 Terminal block see pg 4 LED 1 Blue If ON the SA 025EQ is being powered see pg 9 LED 2 Red If ON the lock relay is energized see pg 8 LED 3 Red If ON...

Страница 4: ...holes located on the side of the unit to a mounting surface Normally energized Screen print refers to energized state as normal Remote alarm relay output 10A 24VDC Form C Relay NO NC COM see pg 8 Loc...

Страница 5: ...relocked by a reset device connected to the Reset Input For information on connecting a reset device see pg 4 Wiring Diagram This reset device is often a momentary spring loaded key switch BOCA Mode T...

Страница 6: ...h at the bottom right of the circuit board Power Up Mode DIP Switch 1 There are two types of power up modes These modes determine the relocking status in case of a power loss Programmed Relock DIP Swi...

Страница 7: ...al alarm pulses during the pre delay gradually pulsing faster until the end of the pre delay time The local alarm will continue signaling steady 5 seconds after the lock has been released When set OFF...

Страница 8: ...e pg 7 LED 4 red is on when the local alarm output is active Lock Relay Output The SA 025EQ is equipped with a 10A 24VDC Form C dry relay output that can be used with a fail safe or fail secure lock T...

Страница 9: ...e bypass input is used to bypass the SA 025EQ and allow unrestricted entry and exit via the door When the bypass input is activated the lock will immediately release It will remain released until the...

Страница 10: ...ted to the reset input This device will manually reset the lock 4 A spring loaded switch is connected to the pre delay bypass input This will allow any authorized user immediate access to the protecte...

Страница 11: ...mon terminal is connected to a positive voltage and the normally closed terminal is connected to the SA 025EQ s initiate input 3 An audible indicator sounds during the pre delay time to alert the user...

Страница 12: ...rkmanship The sole obligation of SECO LARM and the purchaser s exclusive remedy shall be limited to replacement or repair only at SECO LARM s option In no event shall SECO LARM be liable for any speci...

Отзывы: