Inverter power supply user’s manual
2-2
equipment faulting.
z
Standard RS232 communication port: the unit can be controlled and managed by
the monitoring software.
z
Connect external SNMP card to transmit the data between the unit and PC.
2.3 Specification and Technical Data
2.3.1 Technical Data
Rating
500VA
1000VA 1500VA 2000VA 3000VA 4000VA 5000VA 4000VA 5000VA
Rated
DC Input Voltage
48V/110V/220V
110V/220V
48V
DC Operating Range
48V/110V/220V -18%
~
48V/110V/220V +25%
Input Reflected Noise
Input voltage and load current rated: less than 10%
AC Input Voltage
230V-25%
~
230V+20%
Input Frequency
50Hz±10%
AC Output Voltage
230V±2%
Output
Frequency 50Hz±0.1%
Rated
Output
Current 1.7A 3.5A 5.2A 7.0A 10.4A 13.9 17.4 13.9 15.2
Power Factor
0.8
0.7
THD
≤
3%
Transient Response
Load from 0 to 100%
,
less than 30ms
Bypass Transfer Time
<
5ms
Overload
AC mode
:
120%/3min
,
150%/30sec
INVERTER mode
:
120%/30sec
,
150%/10sec
Efficiency
>
88%
Protection
Overload – short circuit – overvoltage – undervoltage – thermal
Interface LED+LCD
Communication Port
RS232
Dry Contact
Yes
Electric Strength
Conform to EN62040-1-1
Noise
(
1m
)
≤
45dB
Ambient Temperature
(℃)
-10
℃
~
45
℃
Relative Humidity
0-95% no dew
Altitude
(
m
)
<
1500
Rack
W×H×D
(
mm
)
482×88×250 482×88×330
516×88×320
Weight
(
Kg
)
5.7 6.2 6.5
9 9.9 12.5 13.5 13.5 14.7
Tower
W×H×D
(
mm
)
158.5×214.2×461 183.5×293×506
183.5×293×570
Weight
(
Kg
)
7.6 8 8.3 12 12.9 14 15 14 15
Содержание TP600 Series
Страница 1: ...TP600SERIES INVERTER POWER SUPPLY USER MANUAL ...
Страница 10: ......
Страница 13: ...Inverter power supply user s manual 3 3 Rack professional model 0 5 1 5KVA 2 5KVA ...