Inverter power supply user’s manual
2-3
2.3.2
DC input voltage and operate range
Rated
voltage
12V 24V 48V 110V 220V
Power ON voltage
10.5
~
14.8 21
~
29.5 42
~
59.5 96
~
136 192
~
272
DC operated range
10
~
14.8 20
~
29.5 40
~
59.5 91.5
~
136 183
~
272
Low warning voltage
11
22
44
101
202
Notes:
1. To protect battery
,
TP600 only powered ON as battery voltage in DC operated
range.
2. When battery voltage is lower to the level of warning point then audible alarm is start up.
In case the battery voltage is lower than the limit, unit will shut down.