If the barometer height, pressure and temperature of the gas deviate very much from the normal values this must 

be taken into account as follows:

f

=

273+t

.

1013,25

273

B+P

u

t

=

Temperature of the gas at the gas meter (15°C)

B

=

Barometer height  (945 mbar)

P

u

=

Pressure of the gas at the gas meter (15,0 mbar)

f

=

273+15

.

1013,25

273

945+15

f

= 11,1

The gas volume read on the gas meter actually reads 1,11 

.

 

 

12,9 = 14,4 m

3

/h.

Net caloriic value

Gas quality

kWh/Nm

3

kJ/Nm

3

kcal/Nm

3

Natural gas

10,3

37 144

8 865

Propane

26,0

93 647

22 350

Butane

34,3

123 571

29 492

Town gas

4,9

17 653

4 213

Bio gas

7,0

25 219

6 019

V

=

Gas volume Nm

3

/h

Q

=

Boiler output 120 kW

H

u

=

Caloriic value of the gas A. 37 144 kJ/Nm

3

, B. 10.3 kWh/Nm

3

η

=

Expected eficiency 90%

Ex. A

v=

Q .3 600

=

120 . 3 600

12,9 Nm

3

/h

H

u

 

· 

η

37 144 . 0,90

Ex. B

v=

120

12,9 Nm

3

/h

10,3 · 0,90

Example how to calculate the gas volume (natural gas)

DETERMINATION OF GAS VOLUME FOR THE INSTALLATION

Speciications on natural gas, town 

gas and bio gas vary. For more exact 
information please contact the gas 
distributor.

172 305 54  08-01

FUNCTION, 2-STAGE DESIGN

Air adjustment

The damper motor turns the damper 

between three pre-set positions: fully 

closed, low load, full load. These 
positons are controlled in the motor 
by cams of different colours. The 
black cam controls the gas valve for 
full load.

Low load:

Adjust the operating switch to full 

load (ll).

*  Reduce the air volume: 

 

Turn orange cam towards 0°

*  Increase the air volume:

 

Turn orange cam towards 90°

Adjust the operating switch back to 

low load and check the air volume.

Full load

Adjust the operating switch to low 

load (l).

*  Reduce the air volume:

 

Turn red cam towards 0°

*  Inrease the air volume:

 

Turn red cam towards 90°

If the red cam is moved, change the 
black cam as much.

Adjust the operating switch to low 

load and check that the correct air 
volume has been obtained.

Note!

 

The blue cam is the limit position for 
fully closed damper and it is normal-
ly not necessary to change it.

Low load (orange)

Full load (red)

Closed damper (blue)

Solenoid valve full load (black)

If  the  air  volume  needs  changing: 

Remove the cover of the damper 
motor and change the position of the 
cams by turning them with the tools 
accompanying the burner.

Содержание BG 700-2

Страница 1: ...178 001 80 Installation and maintenance instruction BG 700 2...

Страница 2: ......

Страница 3: ...p is installed before servicing Take great care when servicing Trap and pinch risks can be present The boiler s sound level can exceed 85 dBA during operation Use ear protectors when present in the bo...

Страница 4: ...eclare under our sole responsibility that the product name type or model batch or serial number possibly sources and number of items BG100 BG150 BG200 STG120 STG146 BG300 BG300LN BG400 BG400LN BG450 B...

Страница 5: ...s not suficient Increase the lue gas temperature by increasing the gas supply Insulate the chimney REMEDY CAUSE 4 4 927 230 A 199 820 403 513 781 403 413 Capacity chart according to EN 676 Out range T...

Страница 6: ...sations at start The ignition electrodes are wrongly adjusted Readjust The gas pressure is too high Check and adjust by means of a pressure gauge and a pressure adjustment valve The lue gas side is bl...

Страница 7: ...relay defective Replace Air pressure switch incorrectly adjusted or defective Check the adjustment and readjust No reponse as the cams of the servomotor are not correctly adjusted or out of position T...

Страница 8: ...nly be ensured by the correct combined effect of the three factors electricity gas low and combustion air Should any of these factors change troubles may arise It has been proved that many troubles ha...

Страница 9: ...ity gasandair supply Should there be any changes intheratiobetweenthesethreefactors there is a risk of break downs It has been proved that most break downs are caused by simple faults Before callingth...

Страница 10: ...e reason for a low ionisation current may be leaking currents bad connec tion to earth dirt or a faulty position of the lame electrode in the burner head Sometimes also a faulty gas air mixturemaycaus...

Страница 11: ...ner is converted to ire another gas quality it must be re commissioned If town gas is to be ired the combustion head must be converted and the gas train adjusted to suit e g a larger gas armature or a...

Страница 12: ...nd the motor will be dead Remove the link from the gas pressure switch after the test is inished 172 205 34 07 01 Leakage control Gas train Noteon2 stageandmodulatingburn ers that during the pre purgi...

Страница 13: ...ipple inlet pressure 11 Test nipple pressure after governor 12 Test nipple before governor 13 Filter Max inlet pressure 360 mbar Adjustable governor pressure 405 412 S50 4 50 mbar 415 420 S20 4 20 mba...

Страница 14: ...formation please contact the gas distributor 172 305 54 08 01 FUNCTION 2 STAGE DESIGN Air adjustment The damper motor turns the damper between three pre set positions fully closed low load full load T...

Отзывы: