HANDING OVER OF THE INSTALLATION
172 305 17 07-01
–
Make repeated start attempts to
ensure that the adjustments
function.
–
Close the ball valve during
operation to check that the gas
switch switches off at the set
value.
–
Remove the hose for the air
pressure switch to check that
the burner locks out.
–
Check that all protective covers
and measurement nipples are
mounted and fastened.
–
Fill out necessary test reports.
–
Instruct the persons in charge
of the operation on the service
and maintenance of the installa-
tion and what to do should any
troubles occur.
–
Inspection and service must
only be carried out by author-
ized people.
Fault location, functional troubles
Trouble free operation is dependent
on three factors: electricity, gas and air
supply. Should there be any changes
in the ratio between these three factors
there is a risk of break downs. It has
been proved that most break downs
are caused by simple faults. Before
calling the service engineer, the following
should therefore be checked:
–
Is the gas cock open?
–
Are all fuses in order and the
current switched on?
–
Are the thermostats correctly
set?
–
Are pressostats, overheating
protection etc. in operating posi-
tion and not locked-out?
–
Is the gas pressure suficient?
–
Is the gas burner control in start
position?
–
Has the gas control or the motor
protector locked out? - Reset.
–
Is the circulation pump in opera-
tion?
–
Is there a supply of fresh air to
the installation?
If integral components are of a
different make from what is stated
in this manual, see the enclosed
loose-leaf.
172 425 35 07-01
D
e
si
g
n
w
it
h
o
u
t
A3
D
e
si
g
n
w
it
h
o
u
t
S1
0
ELECTRIC EQUIPMENT
Gas burner control:LFL1...
Wiring diagram
1(2)
D
a
mp
e
r
p
o
si
ti
o
n
Содержание BG 700-2
Страница 1: ...178 001 80 Installation and maintenance instruction BG 700 2...
Страница 2: ......