GS-IOB-230VAC Installation lnstructions
Table 1
Parts List
ltem
Quantity
AC Circuit Breakers, single-pole (SO A, 250 Vac)
4
with 6-32 x ¼" screws installed
Label Set
1
Installation lnstructions
1
Hardware Kit:
►
Bus Bars
3
►
Bus Bar lnsulators, Blue
2
►
Bus Bar lnsulators, Brown
6
►
Mechanical Bypass Plate, Red
1
►
2
Mechanical Bypass Brackets, Red
►
Self-Tapping Screws, 10-32 x ½"
7 (1 extra)
►
Machine Screws, 6-32 x 3/8"
4
Conductors:
►
Wires, Labeled, Brown
6
►
Wire, Labeled, Blue
1
►
Wires, Short, Dual-Ring Terminal, Brown
2
►
Wire,Green
1
lnstalling the Bus Bars
The GS-IOB-230VAC has enough parts to install up to three AC bus bars in an
enclosure. To install a bus bar in the GSLC:
1.
Select one bus bar and two brown insulators.
Fit one insulator onto each end of the bus bar.
2.
Insert one self-tapping 10-32 x ½" screw
through the hole on each insulator. Seat
these screws in the GSLC chassis and
screw them in. These screws require a
large amount of torque to start.
3.
Apply the correct label from the label
set to the chassis near each bus bar for
identification purposes. Figure 2 shows
the standard locations for these bus
bars. Figure 5 on page 8 shows the
intended label positions.
Figure 2 Bus Bar Positions
NOTE: The neutral and ground bars are already installed. However, the neutral
insulators are white. For systems where blue is standard, replacement blue
insulators are provided in the kit.
[]]
900-0146-01 ·00 REV A
IMPORTANT:
lf the bus bars are placed in other locations or if the labels or
electrical use of the bus bars differ from the figure, the wires
included in this kit may not be of sufficient length.