GS-IOB-230VAC Installation lnstructions
5. Tighten until secure, but do not over-tighten.
Brackets
facing
inward
Inner
holes
H
Bypass
assembly
7"°"
Tabs"
�
�
Hole
Figure 4 lnstalling Mechanical Bypass
Once installed, the plate will not allow both circuit breakers to be in the ON
position. The plate can slide to allow one device to be turned on. The upper
circuit breaker allows the inverter's output to deliver power normally to the loads.
The lower one causes the AC source to bypass the inverter directly to the loads.
Basic AC Wiring
The GS-IOB-230VAC comes with six brown and one blue wire that are labeled
according to their intended electrical connection. lt also comes with an
unlabeled green wire and two unlabeled short brown wires. lf the preceding
steps are followed, as weil as the drawing in Figure 5, these wires will have
sufficient length to make the intended connections.
lt is recommended that the wires be connected to the circuit breakers prior to
re-installing the main circuit breaker bracket. To install the wires:
1. Remove the nuts and washers from each circuit breaker, noting the
sequence of the washers.
2. For each of the six wires, install the wire's ring terminal on the
appropriate terminal post for each circuit breaker according to Figure 5.
Typically each post is equipped with two identical star washers. The
ring terminal on the wire should be installed between these star
6
900-0146-01-00 REVA