3. SAFETY (CONTINUED)

The battery features design-specific mechanical, electrical, and electronic / software-
based provisions to minimize any expected risks. These measures include:

•  A functional safety qualified electronic monitoring and control system to ensure safe 

electrical operation (voltage, current and temperature limits).

•  A safe shut off strategy to respond if limits have been violated (voltage, current, and 

temperature).

•  Contactor and fusing strategy to minimize the impact of external short circuits on the 

battery, however arcing cannot be prevented in the most extreme cases.

•  Dedicated handling / lifting points.

•  Dedicated venting solution to respond to potential cell failure in order to mitigate the 

impacts of the resulting outgassing.

To ensure safety follow the safety guidelines below:

•  Operation must only be done in accordance to the limitations within this document.

•  Stop the usage of the battery if there is a crush, pinch, cut or other damage to the 

power cables or power connectors.

•  Keep the battery away from heat sources.

•  Keep the battery away from ignition sources.

•  Do not operate the battery in a hazardous location like flammable or explosive 

environment.

•  Store only in monitored areas with suitable fire control and protection per local 

requirements, e.g. local fire regulation and building insurance requirements

•  Operate only in monitored areas with suitable fire control and protection per local 

requirements, e.g. local fire regulation, building insurance requirements

•  Operation must only utilize EnerSys

®

 qualified hardware and software as delivered 

and installed by EnerSys personnel (no customizations are allowed).

•  Charging must only be performed with EnerSys approved chargers for NexSys

®

 iON 

batteries.

•  Handling and storage must be in a dry environment.

•  Prevent immersion of the battery into water.

•  Handling and service of the battery requires proper training of EnerSys approved 

technicians with appropriate rated tools and personal protective equipment.

•  In the case in which the battery has been operated or stored outside of the allowable 

limits as stated by this document, cease operation and contact EnerSys.

•  In the case of any error that cannot be reset – do not continue operation of the 

battery until support and direction is provided by EnerSys.

The EnerSys NexSys iON battery is a sealed product, however in case of cell damage 
within the battery there is still the chance of electrolyte leakage, as well as other 
hazards. Please follow the directions below if any of the following incidents take place. 
Additional information can be found in the Lithium-ion Battery (Module) SDS:829515.

•  If leaked electrolyte comes into contact with a person’s skin or eyes, rinse the 

affected areas with clean water for at least 15 minutes. Then in all cases, immediate 
medical attention must be obtained.

•  If leaked electrolyte comes into contact with the mouth, or is swallowed, rinse out 

the mouth as well as the area around the mouth, then immediate medical attention 
must be obtained.

•  If thermal burns are caused, treat them accordingly; then immediate medical 

attention must be obtained.

4. USAGE

The NexSys iON battery must be used, operated and serviced in accordance with 
these operating instructions. The operating instructions of the truck and battery 
charger are required to be respected in addition to these operating instructions. In 
case the permissible operation parameters of the industrial truck are stricter, the 
truck limits must be respected for usage. For example, the permissible range of the 
battery application temperature does not increase the permissible range of the truck’s 
application temperature. 

When the battery is installed into the truck, the traction connector of the battery is to 
remain connected to the truck at all times. Never charge via the traction connector. For 
charging, the charging plug(s) single or dual must be connected to the EnerSys approved 
charger. Upon plugging in the first charge cable, the traction path is opened so that 
the industrial truck cannot be operated inadvertently. For charging instructions refer to 
Chapter 16.  

4. USAGE (CONTINUED)

In the event of discharging below the usable energy resulting in the battery shutting 
down due to low State of Charge (SOC), there is a feature to allow the truck to be 
operated on a very limited capacity and performance in order to immediately return 
to a matching charger. When a low SOC related tripping of the battery occurs, a 
restart (same as turning the pack on) is allowed to reset the pack once. If the battery 
is not placed on charge as soon as possible and allowed to discharge this limited 
capacity, the battery will once again shut down. 

This time it will be locked out and 

require a service visit.

 This limited capacity is intended to only allow for the truck to be 

driven a limited distance and not be used for any lifts.    

Opportunity charging is highly recommended in order to maximize the daily run 
time capability of the battery. It will also optimize the service life of the battery by 
decreasing the discharge window of the battery during discharge.   

For the NexSys

®

 iON battery, it is acceptable and is actually beneficial for lifetime to 

operate a partial state of charge. 

The battery temperature has an effect on the capacity of the battery. For example, run 
time may be reduced at lower temperatures.

Battery temperatures at the extreme ends of the temperature limits as stated in 
this manual will have an effect on performance, possibly resulting in an unexpected 
shutdown. 

All visual and audible warnings are to be respected and reviewed.  

The battery will go into a hibernation mode after a default of 8h when there is less than 
a default of 3A current draw. It can be reactivated by restarting the battery by the various 
start methods. 

5. ENVIRONMENTAL OPERATION LIMITS

The battery is rated to IP54 therefore do not clean the battery with pressurized water.

Do not use the battery outdoors without suitable weatherproof protection.

The battery must not be operated or stored in conditions where it can get immersed.

The battery storage temperatures are -40°F (-40°C) to 140°F (60°C).

The battery operating temperatures are 14°F (-10°C) to 131°F (55°C).

Keep away from fire, sparks, and heat.

Battery must not be exposed to extended periods of direct sunlight that allow the 
temperature of the battery to rise above the storage and operating temperatures of the 
battery.

Batteries must not be operated in condensing environments.

6. FIRE EXTINGUISHING

In the unlikely event of a thermal runaway, which may result in a visible release of gas 
and/or intensive smoke build-up from the battery, 

evacuate the location immediately 

and contact Emergency Response

. If there is an irritation of the respiratory tract, seek 

immediate medical attention. 

Firefighting operations must be performed based on guidance provided in the Lithium-
ion Battery (Module) SDS:829515 by trained firefighters with full 

personal protective 

equipment

 and self-contained breathing apparatus. Ensure that emergency responders 

are informed that the battery has Lithium-ion chemistry. Any indication of a thermal 
event (gas, heat) requires fire suppression methods to be applied (absence of flame is 
not sufficient to consider the thermal runaway event stopped or extinguished).

Large amounts of spray water and/or complete immersion into water can be used 
effectively to cool the battery and contain a Lithium-ion battery thermal event.

In the case of the battery outgassing or after suppression of the fire, store the battery in 
a safe place outside (access restriction, hazard indications) for a minimum of 24 hours. It 
is recommended to monitor the temperature frequently to detect any potential new heat 
generation. In the instance that a thermal event reoccurs follow the same firefighting 
methods.

7. SAFETY VENTING

In the case of a thermal event, the battery is specially designed with a venting aperture 
to ensure any hot gases are vented AWAY FROM THE OPERATOR in a safe manner.

Содержание NexSys iON 24-L1-20-4.7

Страница 1: ...Owner s Manual www enersys com ADVANCED LITHIUM ION TECHNOLOGY Li ion TECHNOLOGY ...

Страница 2: ...Storage of this battery at cold temperatures below the battery operating temperature must not be allowed Usage or storage of this battery in ambient temperatures above the battery operating range must not be allowed Product is neither intended to be permanently stored nor used exclusively outdoors unless truck is designed for it Battery is designed to be charged indoors in the truck Failure to fol...

Страница 3: ... the EnerSys approved charger Upon plugging in the first charge cable the traction path is opened so that the industrial truck cannot be operated inadvertently For charging instructions refer to Chapter 16 4 USAGE CONTINUED In the event of discharging below the usable energy resulting in the battery shutting down due to low State of Charge SOC there is a feature to allow the truck to be operated o...

Страница 4: ...s of the truck may become necessary This must be performed according to the guidance the industrial truck manufacturer or representative has provided Before installation check that the battery is supplied with the appropriate cables to connect the battery to the industrial truck 10 MECHANICAL INSTALLATION INTO INDUSTRIAL TRUCK CONTINUED Ensure that the battery weight and center of gravity requirem...

Страница 5: ...LED display to allow interaction of the battery if accessible or when a battery is outside of industrial truck The buzzer behavior for the CDI is as follows Warning DOD ON 1s OFF 1s Alert DOD ON 100ms OFF 100ms red LED BMS error 3 ON 100ms OFF 100ms red LED For full truck integration the CANopen connector must be connected from the CDI to the truck NOTE In the cases of full OEM integration the bat...

Страница 6: ... falls below 0 SOC the CDI BDI and or Truck iQ will send both visual and audible alarms to the operator for 10 seconds before disconnecting power allowing the operator to slow and move the truck to a safe location please reference Chapter 13 for details on other non disconnecting SOC warning levels Once this Low SOC level is reached the battery can be reactivated ONE TIME to allow travel to the ne...

Страница 7: ...on the charger prior to disconnecting The battery must not be disconnected while still being charged by the charger After a full charge cycle is complete the charger screen will indicate that charging is complete At this point it is no longer supplying current to the battery and the charge plug s should be disconnected from the battery After completely disconnecting the charge plugs s the battery ...

Страница 8: ...mended to turn the pack on and check the SOC every six months and recharge to greater than 30 SOC if the SOC has dropped below 30 SOC Maximum temperature of long term storage location should be less than 35 C 20 SERVICE AND MAINTENANCE The battery has been designed to be maintenance free However external cabling connectors etc including operator interfaces must be examined periodically as required...

Страница 9: ...ayed check the power cables and ensure there are no issues with the truck 479 Battery short circuit event detected due to external sources 7 Battery turning on while being put under excessive electrical load 14 Battery connected to external device at higher than allowable voltage 62 Battery error due to excessively noisy current from truck 63 Battery error due to excessively noisy current from tru...

Страница 10: ... 36 L1 42 16 2 36 5 28 0 42 0 16 2 444 36 L1 42 20 3 36 5 28 0 42 0 20 3 555 36 L1 46 16 2 36 5 28 0 42 0 16 2 444 36 L1 46 20 3 36 5 28 0 42 0 20 3 555 36 L1 46 24 3 36 5 28 0 42 0 24 3 666 36 L1 46 28 4 36 5 28 0 42 0 28 4 777 36 L1 48 20 3 36 5 28 0 42 0 20 3 555 36 L1 48 24 3 36 5 28 0 42 0 24 3 666 36 L1 48 28 4 36 5 28 0 42 0 28 4 777 36 L1 48 32 4 36 5 28 0 42 0 32 4 888 36 L1 48 36 5 36 5 ...

Страница 11: ...11 ...

Страница 12: ...ution prohibited Trademarks and logos are the property of EnerSys and its affiliates except Android and iOS which are not the property of EnerSys Subject to revisions without prior notice E O E GLOB EN OM NEX ION 1121 www enersys com www experiencenexsys com ...

Отзывы: