background image

6

017-950-B1-001, Rev. A (07/2020)

LED Color

Default Rx Range (dBmV)

Default Tx Range (dBmV)

Green

+10 to -10

0 to +50 

* Blue

+15 to +10 and -10 to -15

+50 to +55

* Red

>+15 and <-15

>+55

7.0 Alpha

®

 DOCSIS

®

 3.1 Transponder and Smart AlphaGuard™ LEDs

7.1  Verify Smart AlphaGuard™ operation as indicated below:

Blue RF LED indicates Rx/Tx Power at a warning level. Make the necessary RF level adjustments.

Red RF LED indicates Rx/Tx Power at an alert level. Make the necessary RF level adjustments.

Smart AlphaGuard

 LED State and Indications

LED Name

Color

State

Indication

Active

Green

Off

No power to SAG

Solid

Unit is on and communicating with power supply or in Rest mode

Flash (50% on / 50% off)

Actively balancing

Flash (10% on / 90% off)

Powersave mode

STRG A 

STRG B 

STRG C 

STRG D 

(ALARMS)

Red

Off

Normal operation

String X not present

Flash (50% on / 50% off 

(Minor Alarm)

High delta mean

Check battery alarm

Solid (Major Alarm)

String X missing

All flash (10% on / 90% off)

Stuck relay detected

7.2  Verify Transponder Operation

Table 7-2, Transponder LEDs

Table 7-3, Rx/Tx LEDs

Table 7-1, Smart AlphaGuard LEDs

2.  While in self-test mode, use the Smart Display or a true RMS 

voltmeter to verify output.  Output voltages should appear within 

the ranges shown in Table 6-2. 

3.  To halt/cancel a self-test in progress, press and hold the 

TEST

 

button for one to two seconds or change self-test to OFF in the 

Power Config Menu.

4.  After successful completion of the self-test, perform a Standby Test

 

by shutting off the utility breaker and verifying the 

Power Supply goes into

 

STANDBY MODE and supports the load.

5.  After the Standby test, reapply AC voltage and verify the unit transfers back to LINE MODE.

Voltage Regulation (% Range)

Voltage Setting

Fine (-2.5%/+1%)

Coarse (-5%/+1%)

89VAC

86.77VAC / 89.89VAC

84.6VAC / 89.89VAC

63VAC

61.43VAC / 63.63VAC

59.85VAC / 63.63VAC

Table 6-2, Voltage Regulation

6.3  Self-Test Operation, 

continued

CMM Rx and Tx LED Indications

Step

Communications State

Downstream (DS)

Upstream (US)

Online (OL)

Rx/Tx Power

1

Transponder Initializing/Searching for Downstream DOCSIS

®

 channel(s)

Flashing

OFF

OFF

OFF

2

Downstream channel(s) locked, searching for upstream channel(s)

ON

Flashing

OFF

ON (Green)

3

Upstream channel(s) locked, registering with CMTS

ON

ON

Flashing

ON (Green)

4

CMM fully functional, registration complete

ON

ON

ON

ON (Green)

Verify the CMM LEDs behavior is as follows:

When the CMM is fully functional (step 4 in the table above), the Rx/Tx Power LEDs indicate the RF power levels as 

follows:

Содержание Alpha Broadband UPS

Страница 1: ...e contains a ferroresonant transformer AC oil capacitor line isolation relay Power Distribution Module and EMC Filter board Intelligent Inverter Module Required for standby operations and contains cir...

Страница 2: ...standard options Refer to the technical manual for additional details on advanced status monitoring using the SFP optical port The EMM supports the Smart Display functionality and provides the communi...

Страница 3: ...d insert terminals If using a spacer for the in line fuse link use 1 4 20 x 1 25 4 mm bolts CAUTION 3 0 Output Voltage Reconfiguration Procedure Tools Required Small flat blade screwdriver 1 To access...

Страница 4: ...nput and Output Voltage Current 2 Describes Power Supply Mode of Operation 3 Describes Status of Functions 4 Functionality top level menu PWR BATT COMM and APPS 5 Softkeys Menu driven system configura...

Страница 5: ...m LED Normal Operation On Off Minor Alarm Flash Off Major Alarm Flash Flash Output Off Off Flash OUTPUT ALARM TEST A Self Test Fail alarm will be activated and appear on the Smart Display and Transpon...

Страница 6: ...MS voltmeter to verify output Output voltages should appear within the ranges shown in Table 6 2 3 To halt cancel a self test in progress press and hold the TEST button for one to two seconds or chang...

Страница 7: ...ress 192 168 100 1 into the web browser s address field 4 The transponder s web server home page will appear A Static IP address 192 168 100 2 may need to be set on your network interface card to conn...

Отзывы: