017-950-B1-001, Rev. A (07/2020)

Quick Start Guide

Fig. 1-1, Main features of the XM3.1-HP Series Power Supply

Introduction

This guide briefly describes the XM3.1-HP power supply and provides procedures with regard to the ins tallation of the 

power supply, battery connection, the Smart Display, initial s tartup and tes t, battery configuration and verification of 

successful ins tallation.  For detailed information, refer to the XM3.1-HP Broadband UPS™

 

Technical Manual available at 

www.alpha.com.

Audience

This guide is intended for experienced, qualified and licensed ins tallation personnel familiar with the mechanical and 

electrical requirements of enclosure and power supply sys tems.  Review the support documentation on the website to 

become familiar with the features and functions of the equipment in this sys tem before proceeding.  Failure to ins tall 

and/or use this equipment as instructed in the sys tem documents can result in a hazard to personnel or damage to the 

equipment.  This sys tem is only serviceable by qualified personnel. 

1.0 Overview

The Intelligent Broadband UPS™ is comprised of the following:

Transformer Module —

 Acts as a stand-alone line conditioner.  The transformer module contains a ferroresonant 

transformer, AC oil capacitor, line isolation relay, Power Distribution Module, and EMC Filter board.

Intelligent Inverter Module —

 Required for standby operations and contains circuitry needed for the three-to-five-

stage temperature-compensated battery charger, DC to AC inverter, AC line detectors and Smart Display.

Communications Module

 — The Communications Module is populated with the Smart AlphaGuard™ (SAG) 

mounted to the Element Monitoring Module (EMM).  The module also contains an embedded Cable Modem 

Module (CMM) which enables status monitoring and communications.  This module may also be referenced as a 

"transponder" in this guide and supporting technical manuals.

A

B

C

SAG Battery Sense Harness

Required 

Grounded Surge Protector 

(Alpha p/n 162-028-10 or equivalent)

To Headend

RF Drop

1

Output 1 (Primary)

9

Battery Input

2

Output 2

10

Environmental (ENV) Control Connector

3

N + 1 Port

11

Smart AlphaGuard (SAG) Connector

4

AC Power Input

12

SFP Optical Status Monitoring Port

5

Smart Display with Softkeys

13

Ethernet (ETH) Connector

6

Battery Breaker

14

Tamper (TPR) Switch Connector

7

Local/Remote Indicator (LRI) Connector

15

RF Connector 

8

Precision Temperature Sensor (PTS) Connector

NOTICE:

Alpha recommends 

tightening the RF cable 

connector and the cables 

attached to the Grounded 

Surge Protector to a torque 

setting of 10in-lb ± 1in-lb.

10

11

12
13

15

14

A

B

C

1

2

3

4

5

6

7

8

9

Содержание Alpha Broadband UPS

Страница 1: ...e contains a ferroresonant transformer AC oil capacitor line isolation relay Power Distribution Module and EMC Filter board Intelligent Inverter Module Required for standby operations and contains cir...

Страница 2: ...standard options Refer to the technical manual for additional details on advanced status monitoring using the SFP optical port The EMM supports the Smart Display functionality and provides the communi...

Страница 3: ...d insert terminals If using a spacer for the in line fuse link use 1 4 20 x 1 25 4 mm bolts CAUTION 3 0 Output Voltage Reconfiguration Procedure Tools Required Small flat blade screwdriver 1 To access...

Страница 4: ...nput and Output Voltage Current 2 Describes Power Supply Mode of Operation 3 Describes Status of Functions 4 Functionality top level menu PWR BATT COMM and APPS 5 Softkeys Menu driven system configura...

Страница 5: ...m LED Normal Operation On Off Minor Alarm Flash Off Major Alarm Flash Flash Output Off Off Flash OUTPUT ALARM TEST A Self Test Fail alarm will be activated and appear on the Smart Display and Transpon...

Страница 6: ...MS voltmeter to verify output Output voltages should appear within the ranges shown in Table 6 2 3 To halt cancel a self test in progress press and hold the TEST button for one to two seconds or chang...

Страница 7: ...ress 192 168 100 1 into the web browser s address field 4 The transponder s web server home page will appear A Static IP address 192 168 100 2 may need to be set on your network interface card to conn...