background image

5

017-950-B1-001, Rev. A (07/2020)

6.2  Battery Configuration

1.  From the Operation Normal screen, press the 

BATT

 softkey to open the BATTERY INFO menu. 

2.  Press 

ENTR

 to open BATT CONFIG Menu.  The BATT MHOS screen opens*; press 

ENTR

 to access the first battery 

in the string, for example, (A1).  The first digit will be cycling on and off.  Press the 

UP 

arrow key to set the value of 

each digit as recorded at the time the batteries were installed.  Once the correct value is set, press 

ENTR

 to advance 

to the next digit.  Use the 

UP

 

arrow key as before to set the value.  Repeat for each following digit. When complete, 

press 

ENTR

 to return to the BATTERY MHOS screen.  Press the 

DOWN

 

arrow key to select the next battery in the 

string and repeat the MHOS setting process.

3.  Once the MHOS values for each battery have been set, press 

ESC

 to return to the BATTERY CONFIG MENU.

4.  Press the 

DOWN

 arrow key to select the next line item for adjustment: BATT DATES.

5.  Press 

ENTR

 to select battery and advance to DATE SET screen.  Press 

ENTR

 to select Batt A1 date. Select 

ENTR

 

and key in the dates recorded from the battery labels at the time of installation.  Press 

ESC

 to return to the DATE SET 

screen and the down arrow to select the next battery.  Repeat the above steps for each remaining battery.

6.  Press 

DOWN

 

arrow softkey and select BATT

 

MODEL and from the submenu, select the battery type installed.

7.  Press 

ENTR

 to return to the Battery Config menu and select NUM BATT STRINGS and enter the correct value.

8.  Press 

ENTR

 to accept new data.

9.  Press 

ESC

 to return to the OPERATION NORMAL screen.

10. Switch SPI/ALT 

ON

 and verify the XM3.1-HP is supplying to the load.

Condition

Output LED

Alarm LED

Normal Operation On

Off

Minor Alarm

Flash

Off

Major Alarm

Flash

Flash

Output Off

Off

Flash

OUTPUT

ALARM

TEST

A Self-Test Fail alarm will be activated and appear on the Smart Display and Transponder web page if the XM3.1-

HP detects one or more defective battery strings or problem with the Inverter Module.  Replace batteries or module 

as required.  This is a latched alarm and power cycling the Inverter Module will not clear the alarm.  This alarm can 

only be cleared by successfully running in self-test for a minimum of one minute.

For power supply installations that may not have utility power available due to new construction or extended service 

interruptions, it is recommended to disconnect the batteries from the power supply until the site is fully functional.  

It is not recommended to have the power supply battery circuit breaker in the off position with batteries connected 

and no utility power connected for extended periods of time.  A warning will display on the Smart Display when this 

condition is detected.

NOTICE:

NOTICE:

6.3  Self-Test Operation

The power supply should be operating correctly with no alarms present.  

Use the Smart Display to verify Normal and Communication Information.  

Verify Test Duration setting in the PWR CNFG menu screen.

1.  Press and hold the 

TEST

 button for 1 to 2 seconds to start self-

test.  The test will run for a preset time (5-180 minutes, set in the 

PWR CNFG Menu).  Self-test can also be entered by setting self-test 

to ON in the PWR CNFG Menu.  Additionally, the self-test can be 

configured to perform a deep-discharge of 10%, 20%, 30%, 40% and 

50% of battery capacity.  When the deep discharge is complete, it will 

revert back to the Timed Test.

Fig. 6-5, Test Button

Table 6-1, Alarm Indicators

* Battery MHOs and Date code should only be set after the transponder is online, as indicated by the "OL" LED showing a steady ON state. 

Содержание Alpha Broadband UPS

Страница 1: ...e contains a ferroresonant transformer AC oil capacitor line isolation relay Power Distribution Module and EMC Filter board Intelligent Inverter Module Required for standby operations and contains cir...

Страница 2: ...standard options Refer to the technical manual for additional details on advanced status monitoring using the SFP optical port The EMM supports the Smart Display functionality and provides the communi...

Страница 3: ...d insert terminals If using a spacer for the in line fuse link use 1 4 20 x 1 25 4 mm bolts CAUTION 3 0 Output Voltage Reconfiguration Procedure Tools Required Small flat blade screwdriver 1 To access...

Страница 4: ...nput and Output Voltage Current 2 Describes Power Supply Mode of Operation 3 Describes Status of Functions 4 Functionality top level menu PWR BATT COMM and APPS 5 Softkeys Menu driven system configura...

Страница 5: ...m LED Normal Operation On Off Minor Alarm Flash Off Major Alarm Flash Flash Output Off Off Flash OUTPUT ALARM TEST A Self Test Fail alarm will be activated and appear on the Smart Display and Transpon...

Страница 6: ...MS voltmeter to verify output Output voltages should appear within the ranges shown in Table 6 2 3 To halt cancel a self test in progress press and hold the TEST button for one to two seconds or chang...

Страница 7: ...ress 192 168 100 1 into the web browser s address field 4 The transponder s web server home page will appear A Static IP address 192 168 100 2 may need to be set on your network interface card to conn...

Отзывы: