Oil Heat – Eighteenth Edition – June 2015
27
DIAGNOSTICS with the DIGITAL MANAGER
Manager Lights
Temperature
Description
DIAGNOSIS
(1)
Normal Operation
Thermostat calling
No Zone output lights
(2)
Normal Operation
No Thermostat Call
Zone Outputs On
Circulator
On
(3)
Normal Operation
Hot Water Calling
Thermostat
Calling
Only Output zone is hot water
(4)
Problem
No Lights on Manager
(5)
Problem
Burner
Light
On
Burner Not Running
(6)
Problem
Inducer Light does
not come on
(7)
Problem
Zone Output Light On
Zone Valve does not open
(8)
Problem
Dim light on thermostat
calling.
Burner Restart: A two (2) minute delay is built into the control. (45 seconds for a Hot Water call).
Reset the Digital Manager by turning system switch off and back on again
.
Service Board Mode- With power off, remove the RED lead of the temperature sensor to run in this mode.
A Service Board for temporary operation without Manager is available. This is interchangeable with the Classic
and Digital Managers. Rebuilt Managers are available for nominal rebuild charge and require the return of a
Manager (Manager must be rebuildable).
Preheat cycle – zones will open when
boiler return is above 140
o
F (150
o
F if
option switch 1 is on).
Return temperature dropped during
call. Zones close until boiler is up to
temperature.
Check
Main
Power
Check Transformer for 24 volts
Check A1, A2 terminals on Manager for
24 volts
Check boiler temperature and high
limit aquastat. Set higher for test.
Check for boiler circulation failure.
Check burner for power in.
Check burner and/or cad cell relay.
Reset if necessary. If still no heat,
jumper TT terminals on burner relay
to test burner.
Check option switch 2:
“ON” = Power Venting
“OFF” = Chimney Venting
Check for 24 volts between 24VAC
common and zone in question.
Check zone valve or circulator on
zone calling for operation.
A dull yellow light is common with a
power-stealing thermostat. It is not
a call for heat and can cause erratic
operation of outputs.
Check option switch 10, hot water
priority. “ON” sets up to 25 minutes
priority to hot water zone, then other
calling zones open.
Energy Recovery cycle will run until
time or return temperature is reached.
(See option switches 5 through 8.)