Oil Heat – Eighteenth Edition – June 2015
15
Figure 4A
ELECTRICAL CONNECTION - LINE VOLTAGE
POWER SUPPLY: 120 VOLT 60 HZ, 7.5 Amperes
System 2000 requires 120 VAC. The supply voltage must be within 108 VAC min / 132 VAC max for reliable operation
of the boiler and the Manager. An easy way to check the supply voltage is to plug a voltmeter in at the service outlet
located on the side of the system junction box.
DANGER:
Make All Connections with
Power Off
at Main Circuit Box
Figure 3A:
Connect power from a separate 15 AMP fused circuit. Install 3
rd
wire grounding for proper bond between all
electrical accessories. The system switch is included so power can be shut off at the unit for servicing.
Pigtails are provided for the line voltage power connection. Connect black pigtail to hot, white pigtail to neutral, and the
green pigtail to ground.
WARNING:
The junction box is wired at the factory with the service outlet always powered, even with the System
Emergency Switch turned off. To have the service outlet controlled by the System Emergency Switch, move the service
outlet black lead to top lug of system switch. A low water cut-off is included on all new systems, but may be field installed
if required by local codes and is available from Energy Kinetics if not included.
LOW VOLTAGE WIRING
DIGITAL MANAGER OPERATES ONLY ON 24 VOLTS 60 HZ POWER
WARNING: Make All Connections with Power Off at Main Circuit Box
A typical low voltage wiring diagram for the Digital Manager is shown in
Figure 4A
. Thermostats must be located
on inside walls away from cold drafts, windows or heat from fireplaces, appliances or sunlight. Set thermostat heat
anticipators to 0.1 amps (or "gas" if gas/electric option). Call Energy Kinetics to request alternate low voltage wiring
diagrams to handle special situations such as air handler wiring, heat pump wiring, isolation relays for thermostats, and
isolation relays for heat motors or circulators, etc.
The single 24-volt/50VA transformer is suitable for the Digital Manager and five zone outputs (zone valves or
relays).
NOTICE:
Additional load such as extra valves may require greater transformer capacity. To add transformers,
wire in parallel as follows: wire terminal “A” on one transformer to “A” on the other. Repeat with other low voltage terminal
“B”. Be sure to verify 24VAC output from all transformers.
The Digital Manager is designed to heat domestic water and up to four (4) heating zones. Use Energy Kinetics
supplied zone valves with two wire connections. For more than four heating zones, use Energy Kinetics 12 zone
expanded Digital Manager, or call Energy Kinetics for alternatives.
LOW VOLTAGE WIRING DIAGRAM
INSTALL DIGITAL MANAGER
The Digital Manager is shipped in its own protective shipping box.
NOTICE:
The option switches can be set very
easily before the Manager is installed. Locate the pre-wired quick connectors fastened to the front of the junction box by
two cable ties. Cut the two cable ties and discard. Fasten the Digital Manager to the junction box with the four corner
screws. Slide the two quick connectors onto the Digital Manager. Label each zone on the manager, using the adhesive
labels supplied.
ZONE VALVE 3
Z3
A1
TRANSFORMER
24V POWER
RED
FROM
ZONE 4
TEMP
LEADS
SENSOR
BLACK
SILVER
TE
MP.
SE
NS
.
T4
R
CAUTION
MAKING ANY CONNECTIONS
READ INSTRUCTIONS BEFORE
24 VAC CONNECTION ONLY.
B
S
A2
4
TO BURNER RELAY
MAIN CIRC RELAY
MONITOR
CIRCULATOR
160
130
120
100
140
150
190
POWER
170
ONLY
CHIMNEYLESS
BURNER
INDUCER
4
CIRC
B2
T
IND
B1
24VAC
T
FIELD WIRING
FACTORY WIRING
ZONE 3
ZONE 1
ZONE 2
80
70
60
90
THW
T2
T3
T1
2
3
1
HOT WATER TANK
HW CIRC RELAY
ZONE VALVE 2
ZONE VALVE 4
2
3
1
HOT WATER
Z4
Z1
Z2
ZHW
ZONE VALVE 1
*Field Wiring terminated to input terminal A1 and to output terminal 24VAC are to
be wired into the open lugs provided at those locations.