Accel CS Boiler - Gas Heat - Eighth Edition – January, 2015
48
Lockout History
•
Records last 15 Lockouts
•
Using the arrow/cursor buttons – navigate to the Lockout record of choice and push the
OK
button to
view Lockout details stored at the time the Lockout occurred.
•
Lockout history is stored in non-volatile memory. History will be retained even when the
power is off.
Lockout History Record
•
Display detailed information for each Lockout.
•
Pressing
Back
or
OK
buttons transitions back to the
Lockout History
screen.
Alert History
•
Records the last 15 Alert messages.
•
Using the arrow/cursor buttons – navigate to the Alert record of choice and push the
OK
button to view Alert details stored at the time the Alert occurred.
•
Alert
Alert History Record
•
Display detailed information for each Alert.
•
Pressing
Back
or
OK
buttons transitions back to the
Alert History
screen.
LOCKOUTS, HOLDS, AND ALERTS
The Honeywell Sola boiler control has a display designed to inform the user about lockout, hold, and alert conditions.
Each condition has a code that is displayed along with an English sentence that briefly describes what the code means.
Lockouts:
It is very important to note that lockouts must be manually reset and will usually require service attention.
The history of lockout events is stored in non-volatile memory, which means that up to fifteen lockout events can be
stored and displayed, even if the power to the boiler control is turned off and back on.
Holds and Alerts:
On the other hand, holds and alerts are meant to be informative about the state of the boiler and will
automatically reset themselves once the hold or alert condition has cleared. It is very important to note that holds and
alerts in general are not error conditions and rarely would require any type of service attention. Since holds and alerts are
not safety related conditions, the history of the last fifteen holds and alerts is stored in volatile memory, which means that
the hold and alert memory will be lost if the power to the boiler control is turned off and back on.
Best Practice:
Be sure to write down, or take a picture of, the history screen showing the holds and alerts before turning
off the power to the boiler.
109 Ignition Failed
0 None
0 None
0 None
0 None
0 None
Lockout History
Lockout 109
Ignition failed
Cycle: 134 Hours:0
Time: 4 sec
Start: Direct Burner Ignition
First out: None
Outlet: 70°F
Inlet: 70°F
DHW: OPEN
Lockout History Record 1
29 Burner switch was turned off
0 No Alert
0 No Alert
0 No Alert
0 No Alert
0 No Alert
0 No Alert
0 No Alert
Alert Log
Alert 29
Burner switch was turned off
Cycle: 134 Hours:0
Alert Log Record 1
Содержание EK1C
Страница 60: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 59 DRAWINGS WIRING...
Страница 61: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 60 DRAWINGS WIRING...
Страница 62: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 61 DRAWINGS WIRING...
Страница 63: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 62 DRAWINGS WIRING...
Страница 64: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 63 DRAWINGS WIRING...
Страница 65: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 64 DRAWINGS WIRING...
Страница 66: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 65 DRAWINGS WIRING...
Страница 71: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 70...
Страница 72: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 71 THIS IS A BLANK PAGE...