Accel CS Boiler - Gas Heat - Eighth Edition – January, 2015
38
When lit, this light indicates 24 volts between the terminals 24VAC and IZ. This provides power to a 24-volt injection
zone valve if the system is so equipped. When this light is on, the Condensing Energy Manager will tell the Sola control
to turn on the Loop Circulator relay output. Refer to the option switch settings page for more information on how to use
this feature.
F) Temperature Display:
The Condensing Energy Manager displays the boiler supply temperature, not the boiler return temperature. The Sola
display will show the boiler supply and return temperatures, the outdoor temperature and the stack temperature.
CONDENSING ENERGY MANAGER OPTION SWITCHES
Located on back of Condensing Energy Manager.
Option Switch Settings
Option
Switch
Description
Function ( OFF is the factory default for all switches)
OFF = Slide to Front
ON = Slide to Rear
1
Zone 1 Output.
Normal or Injection.
Z1 is the only zone heating
output for zone 1.
Loop circulator, injection zone valve
and Z1 are all enabled.
2
Zone 2 Output.
Normal or Injection.
Z2 is the only zone heating
output for zone 2.
Loop circulator, injection zone valve
and Z2 are all enabled.
3
Zone 3 Output.
Normal or Injection.
Z3 is the only zone heating
output for zone 3.
Loop circulator, injection zone valve
and Z3 are all enabled.
4
Supply temperature
settings controlled by
Manager or Sola.
Manager controls boiler
supply temperature using
Auto Express settings (see
switch 5).
Enables custom boiler supply
temperature settings to be entered
using Sola display.
5
Manager Auto Express
temperature settings.
Switch 4 must be
turned off.
Outdoor reset max./min.
boiler supply setting =
160°F/120°F. Boiler supply
setting = 182°F during
DHW call.
Outdoor reset max./min. boiler supply
setting = 180°F/140°F. Boiler supply
setting = 182°F during DHW call.
6
SmartBoost™
Enables SmartBoost™
Disables SmartBoost™
7
SmartBoost™ Delay:
Option switch 6 must
be turned off.
SmartBoost™ will delay
boost function for 25
minutes.
SmartBoost™ will delay boost
function for 45 minutes.
8
Zone 4 purge time.
Zone 4
max. purge = 20 min.
Zone 4
max purge = 5 min.,
and disables MultiPurge™ for all
zones up thru zone 4.
9
Domestic Hot Water
Pump relay output
Enables DHW Smart Pump
relay output and indicator
LED.
Disables DHW Smart Pump relay
output and indicator LED, increases
purge time to 20 minutes and
enables MultiPurge™
10
DHW priority.
DHW priority = 25 minutes. DHW priority = 45 minutes.
NOTE: any zone that is set to 5 minutes max energy recovery time will have MultiPurge™ disabled for
that one zone. In particular, the hot water zone by default will not MultiPurge™.
1 2 3 4 5 6 7 8 9 10
O
N
Looking at Condensing Manager with center
panel down (open).
Содержание EK1C
Страница 60: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 59 DRAWINGS WIRING...
Страница 61: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 60 DRAWINGS WIRING...
Страница 62: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 61 DRAWINGS WIRING...
Страница 63: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 62 DRAWINGS WIRING...
Страница 64: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 63 DRAWINGS WIRING...
Страница 65: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 64 DRAWINGS WIRING...
Страница 66: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 65 DRAWINGS WIRING...
Страница 71: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 70...
Страница 72: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 71 THIS IS A BLANK PAGE...