![ENERGY KINETICS EK1C Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/energy-kinetics/ek1c/ek1c_installation-and-service-manual_2410385023.webp)
Accel CS Boiler - Gas Heat - Eighth Edition – January, 2015
22
VENTING VERTICALLY WITH POLYPROPYLENE
Part No:
Description:
10-0582
Chimney Vent Kit 2in PPs
10-0583
Chimney Vent Kit 3in PPs
10-0586
Chimney Vent Kit 4in PPs
The Accel CS boiler may be installed with polypropylene vent materials
vertically through the roof of a building.
Combustion air may be piped alongside the vertical vent using a dedicated
polypropylene liner or PVC pipe. Combustion air may also be taken directly
from the boiler room, although piping combustion air directly from the
outdoors is the best practice.
Chimney Liner
A masonry chimney will not stand up to the corrosive nature of the flue gas
from a condensing boiler. The chimney therefore must have a liner installed
that complies with UL 1738. An existing chimney may be used as a chase
for an approved liner.
Any chimney liner must be made from AL29-4C stainless steel alloy or
approved polypropylene product that is designed for positive pressure
venting. The chimney liner length must be added to the rest of the flue
piping to determine the allowable maximum length.
Optional Venting parts, order as needed for the job.
Description
Centrotherm
Part No.
DuraVent Part
No.
2” Chimney Liner Kit, with 35 ft of flex
IFCK0235
N/A
3” Chimney Liner Kit, with 35 ft of flex
IFCK0335
N/A
3” Chimney Liner Kit, with 35 ft of flex
IFCK0435
N/A
2” Chimney Liner Kit, order flex separately
N/A
2PPS-FKL
3” Chimney Liner Kit, order flex separately
N/A
3PPS-FKL
4” Chimney Liner Kit, order flex separately
N/A
4PPS-FKL
2” Flex lining, 35 feet
IFVL02035
2PPS-FLEX35
3” Flex lining, 35 feet
IFVL03035
3PPS-FLEX35
4” Flex lining, 35 feet
IFVL04035
4PPS-FLEX35
Notes:
For Centrotherm: Includes all components necessary to line a chimney from chimney termination to base support. Rigid
vent lengths, elbows and adapters required to connect chimney kit base support to appliance are sold separately.
Kit includes 35 feet of flex.
For DuraVent: Use for a vertical flex lining system. Includes black UV resistant chimney cap, rigid flue vent, flex support
bracket, 4 spacers in 3” kits, male and female flex adapters with gaskets, extended support elbow, wall plate and Appliance
adapter. Flex sold separately.
Содержание EK1C
Страница 60: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 59 DRAWINGS WIRING...
Страница 61: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 60 DRAWINGS WIRING...
Страница 62: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 61 DRAWINGS WIRING...
Страница 63: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 62 DRAWINGS WIRING...
Страница 64: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 63 DRAWINGS WIRING...
Страница 65: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 64 DRAWINGS WIRING...
Страница 66: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 65 DRAWINGS WIRING...
Страница 71: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 70...
Страница 72: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 71 THIS IS A BLANK PAGE...