Accel CS Boiler - Gas Heat - Eighth Edition – January, 2015
47
DIAGNOSTICS USING THE ACCEL CS DISPLAY
The
Home
screen shows the current state of the boiler control. At any time, you can press the
Home
button and the display will return to the
Home
screen. The first five rows show the current
temperatures of the system. The next four rows in smaller font show the boiler name, the state of
the control, the demand, and the access status.
Pay particular attention to the state and the demand rows. The state of the control will tell you
what the control is doing at any time, such as pre-purge, ignition, running, or post purge. The
demand row shows ‘CH’ whenever there is a call for heat or hot water to the Sola control. The
demand row will show ‘Standby’ when the boiler is idle, and will show ‘Lead Lag slave’ when the
boiler is cooling off due to energy recovery.
The bottom row will show codes with an English explanation for lockouts, holds, and/or alerts. A lockout will require
manual reset of the control, while holds and alerts will automatically reset when the condition is cleared.
Press the right arrow to move to the Analog sensor screen.
Analog Sensor
Screen
•
Do they all make sense?
•
OPEN
indicates that the sensor is not connected
•
Minimum flame signal is 1 uA
•
Review sensor temperature readings
Press the right arrow again to move to the Digital input/output screen
Digital IO
screen
•
Review digital inputs and outputs
•
Boiler pump (A)
, the main boiler circulator
•
DHW pump (B)
, the bronze Smart Pump
•
System pump (C)
, the primary loop circulator
•
Load Control Input (LCI)
is the Low Water Cut Off input
Press the
Info
button to transition to the Information Screen. Using the arrow/cursor buttons,
navigate to the
Diagnostics
icon and push the
OK
button.
Using the arrow/cursor buttons - navigate to…
•
History
icon and press
OK
button to view the
Alert
or
Lockout History
.
System setpoint
Operating temp
Outlet temp
Inlet temp
Outdoor temp
Boiler name
State
Demand
Access status
No lockout/hold/alert
160°F
158°F
158°F
138°F
13°F
Accel CS
Preignition Time
CH
User
Diagnostics
Analog Sensors
Digital IO
History
Diagnostics
Diagnostics
Outlet temp
Inlet temp
Delta T
DHW temp
Stack temp
Outdoor temp
Fan Speed
Flame Signal
4-20mA input
System sensor
138°F
115°F
23°F
OPEN
117°F
36°F
LOW
8.21µA
OPEN
Outlet
Boiler pump (A)
DHW pump (B)
System pump (C)
Blower/HIS
External Ignition
Pilot valve
Main valve
Alarm
Interlock (ILK)
Pre-ignit Interlock (PII)
Load Control Input (LCI)
STAT (Demand)
Time of Day
Safety relay
Diagnostics
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
On
On
Off
Off
Login
Advanced
Setup
Display
Setup
Quick
Start
Test
Diagnostics
Diagnostics
Содержание EK1C
Страница 60: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 59 DRAWINGS WIRING...
Страница 61: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 60 DRAWINGS WIRING...
Страница 62: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 61 DRAWINGS WIRING...
Страница 63: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 62 DRAWINGS WIRING...
Страница 64: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 63 DRAWINGS WIRING...
Страница 65: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 64 DRAWINGS WIRING...
Страница 66: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 65 DRAWINGS WIRING...
Страница 71: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 70...
Страница 72: ...Accel CS Boiler Gas Heat Eighth Edition January 2015 71 THIS IS A BLANK PAGE...