4. Technical Data
4.1 DC Input
Model
Force 3S
Force 3.6S
Force 4.6S
Force 5S
Force 6S
Max. Recommended DC Power [W]
4500
5400
6900
7500
9000
Max. DC Voltage [V]
600
600
600
600
600
Nominal DC Operating Voltage[V]
360
360
360
360
360
Max. Input Current (input A/input B)
[A]
12.5/12.5
Max. Short Circuit Current (input
A/input B) [A]
15/15
MPPT Voltage Range [Vdc]
80-550
80-550
80-550
80-550
80-550
Start-up Voltage [V]
120
120
120
120
120
No. of MPP Trackers
2
2
2
2
2
Strings Per MPP Tracker
1
1
1
1
1
4.2 AC Output
Model
Force 3S
Force 3.6S
Force 4.6S
Force 5S
Force 6S
Nominal AC Power [W]
3000
3600
4600
5000
6000
Max. Apparent AC Power [VA]
3300
3960
5060
5500
6000
Rated Grid Voltage [Vac]
220/230/240
Rated Grid Frequency [Hz]
50/60,
±
5
Nominal AC Current [A]
13.0
15.7
20.0
21.7
26.1
Max. AC Current [A]
14.3
17.2
22.0
23.9
26.1
Displacement Power Factor
1 (Adjustable from 0.8 leading to 0.8 lagging)
Total Harmonic Distortion (THDi,
Nominal output)
<3%