Solar Inverter | Installer Manual [13]
•
Grid Connection
This series of
Energizer
solar inverters are designed for single-phase grid. Voltage range is 220/230/240V;
frequency is 50/60Hz. Other technical requests should comply with the requirement of the local public grid.
Model
Force 3S
Force 3.6S
Force 4.6S
Force 5S
Force 6S
Cable
4mm²
4mm²
6mm²
6mm²
6mm²
Micro-Breaker
25A
25A
40A
40A
40A
WARNING!
A micro-breaker for max output overcurrent protection device must be installed between inverter and grid,
and the current of the protection device is referred to the table above, any load SHOULD NOT be
connected with the inverter directly.
Step 3: AC Wiring
•
Check the grid voltage and compare with the permitted voltage range (refer to technical data).
•
Disconnect the circuit-breaker from all the phases and secure against reconnection.
•
Trim the wires:
-
Trim all the wires to 52.5mm and the PE wire to 55mm.
-
Use the crimping pliers to trim 12mm of insulation from all wire ends as below.
•
Separate the AC plug into three parts as below.
-
Hold middle part of the female insert, rotate the back shell to loosen it, and detach it from female inset.
-
Remove the cable nut (with rubber insert) from the back shell.
•
Slide the cable nut and then the back shell onto the cable.
L: Brown/Red Wire
N: Blue/Black Wire
PE: Yellow & Green Wire
Please refer to local cable type and color for actual installation.