Electrical connection
Overfill Prevention System SOP300
22
Hauser
z
1
–1yX1
2
3
4
12
Connection example for point level switches
y
1 = HH, 2 = H, 3 = L, 4 = LL, 5 = Leak
z
NC or NO contact, depending on the sensor
1
24 V DC
2
0 V DC
3
Point level "OK" or "Not OK" with 24 V DC signal, depends on sensor, point level "OK" is recommended as
a wire break is reliably detected and the relay adopts a safe state
4
NA
Input signal: point level switch with device error
Connectable point level switches:
Every sensor that has two floating contacts (NEx/Ex(d)). One contact is used for point level
detection and the second contact for the device error.
1
–1yX1
2
3
4
z
z
13
Connection example of point level switch with device error
y
1 = HH, 2 = H, 3 = L, 4 = LL, 5 = Leak
z
NC or NO contact, depending on the sensor
1
24 V DC
2
0 V DC
3
Point level "OK" or "Not OK" with 24 V DC signal, depends on sensor, point level "OK" is recommended as
a wire break is reliably detected and the relay adopts a safe state
4
"Device error" or "No device error" with 24 V DC signal, depends on sensor, "No device error" is
recommended as a wire break is reliably detected and the relay adopts a safe state
Input signal: continuous level
The sensor must meet the following requirements:
• Output signal: 4 to 20 mA for 0 % to 100 % level
• NEx/Ex(d)
• 2-wire sensors (passive) or 4-wire sensors (active)