Applications
Number of measurement points
The number of measurement points vary according to the unit model and application. For further
details, please see the table for applications/measurement points.
In general, the following measurements are possible:
Up to 2 measurement points using the input values (measurements) q, p, T
p
, T
w
, when using
saturated steam then up to 3 measurement points using the inputs q, p/ T
p
, T
w
.
One measurement point is covered by the basic unit. Expansion cards are required if further
measurement points are to be added. Each expansion card is fitted with outputs
(analogue/impulse) for retransmission of process values. Relay outputs are also available.
Diagram/calculation formula
T
W
q
p
T
D
E = q
(p, T
D
)
[h
D
(p, T
D
) – hw (T
W
)]
E:
Heat quantity
q: Operating
volume
:
Density
T
D
:
Temperature in inflow (steam)
T
W
:
Temperature in return (water)
p:
Pressure (steam)
h
D:
Specific Enthalpy of steam
h
W:
Specific Enthalpy of water