6 Commissioning
RMS 621
40
Hauser
Flow installation point
Warm
Cold
Set up in which thermal area the flowmeter is installed for this
application (only active on water heat difference).
On steam/heat differential the installation point is defined as
follows:
Heating: Warm (means steam flow)
Steam production: Cold (means water flow)
!
Note!
On bi-directional operating mode please select the parameters
analogue to the heating mode.
Pressure
Please select
Pressure1-3
Allocate the pressure sensor to the application. Only the
sensors that have already been set up (see "Setup: Pressure")
are available.
Average pressure
10.0 bar
Set up the average process pressure (absolute) in the heating
circuit.
!
Note!
Applicable only on water applications
Temperature
Please select
Temperature 1-6
Allocate the temperature sensor to the application. Only the
sensors that have already been set up (see "Setup:
Temperature") are available.
!
Note!
Set-up not active for differential applications.
Temperature
cold
Please select
Temperature 1-6
Allocation of the sensor that measures the lowest temperatures
in the application. Only the sensors that have already been set
up (see "Setup: Temperature") are available.
!
Note!
Set-up only active for heat differential measurement
applications.
Temperature
warm
Not used
Temperature. 1-6
Allocation of the sensor that measures the highest
temperatures in the application. Only the sensors that have
already been set up (see "Setup: Temperature") are available.
!
Note!
Set-up only active for heat differential measurement
applications.
Minimum temp. diff.
0.0
to 99.9
Set-up the minimum temperature difference. If the measured
temperature difference is lower than this value then the heat
quantity is no longer calculated.
!
Note!
Set-up only active for water heat differential measurement
applications.
Engineering units
Set up the engineering units that will be displayed for each
individual application. (see "set up units")
Sums
Set up the sum counter.
Function (Menu
address)
Parameter set-up
Description
Содержание RMS621
Страница 1: ...BA127R 09 en 08 04 510 04788 Software Version 2 0 Operating manual RMS 621 Energy manager ...
Страница 6: ...RMS 621 6 Endress Hauser ...
Страница 23: ...RMS 621 5 Operation Endress Hauser 23 5 1 2 Display Quick Setup ...
Страница 88: ......
Страница 90: ...www endress com worldwide BA 127R 09 en 08 04 510 04788 FM SGML6 0 ...