Applications
Water/heat differential
(Heating/cooling)
Application areas
Calculation of the heat quantity, which is transmitted to or from a heat exchanger in a water
circuit. Typical application for energy measurement in a heating or cooling network
.
Measurements
Measurement of operating volume and temperature in a water circuit immediately before and
after a heat exchanger (in the inflow and return circuit).
A pressure sensor can also be connected in order to measure the operational pressure in the
circuit. This pressure measurement has no direct influence on the actual calculation (see inputs).
Inputs
•
Inflow: Flow (q), temperature (T
1
)
•
Return: Temperature (T
2
)
Note!
- For an exact calculation of the process values and measurement range limits, a further input value for the
operating pressure of the water network is required. The average operating pressure (p) is a preset value (not an
input signal). The pressure can only be entered as an average signal, even if the pressure is measured using a
pressure sensor.
- The flow meter installation point is selectable!
- The installation point is defined as the warm/cold side and not the inflow/return, as this definition is clear for
all operating modes.
- It is recommended to place the flow meter in a position in the circuit where the temperature is closest to the
ambient (room) temperature.
Calculated values
Calculation of mass flow, heat differential (heat flow or power), temperature difference, Enthalpy
difference, density (IAPWS–IF97 Standard).
Output values/display at unit
•
Heat flow, mass flow, flow (operating volume), temperature 1, temperature 2, temperature
difference, Enthalpy difference, density.
•
Heat quantity sum, mass sum, flow sum.
Outputs
All output values can be transmitted using the output terminals, this means both unchanged
inputs as well as calculated values. Please note that the number of outputs available is dependent
on the unit type.
Содержание RMS621
Страница 1: ...BA127R 09 en 08 04 510 04788 Software Version 2 0 Operating manual RMS 621 Energy manager ...
Страница 6: ...RMS 621 6 Endress Hauser ...
Страница 23: ...RMS 621 5 Operation Endress Hauser 23 5 1 2 Display Quick Setup ...
Страница 88: ......
Страница 90: ...www endress com worldwide BA 127R 09 en 08 04 510 04788 FM SGML6 0 ...