Engineering units
The unit is capable to operate each individual application using different engineering units. The
engineering units for each application are set up in the sub menu
Setup (all parameters)
Æ
Application
Æ
Application ...
Æ
Eng. units
. The following set-up is possible:
!
Note!
The selection of the engineering units for the flow (volume), pressure and temperature is done in
the set-up for each individual sensor.
A definition of the important system engineering units can be found in Chapter 11 "Appendix" of
these operating instructions.
Function (Menu
address)
Parameter set-up
Description
Time base
.../s; .../min;
.../h
; .../d
Time base for the flow engineering units in format: X
per
selected time unit.
Heat flow
kW
MW
kcal/time
Mcal/time
Gcal/time
kJ/h
MJ/time
GJ/time
KBtu/time
Mbtu/time
Gbtu/time
ton (refrigeration)
Defines the heat quantity per preset time unit or the thermal
power.
Heat sum
kW * time, MW * time,
kcal, Gcal, GJ, KBtu,
Mbtu, Gbtu, ton * time
MJ
, kJ
Engineering unit for the heat quantity or thermal energy.
Mass flow
g/time, t/time, ibs/time,
tons(US)/time, tons/time
kg/time
Engineering unit for the mass flow per previously defined time
unit.
Mass sum
g, T, ibs, tons (US), tons
kg
Engineering unit of the calculated mass sum.
Density
kg/dm, Ibs/gal, Ibs/ft
kg/m
Engineering unit for density.
Temperature difference
°C, K, °F
°C
Engineering unit for temperature difference.
Enthalpy
kWh/kg, MJ/kg, kcal, kg,
Btu/Ibs
MJ/kg
Engineering units for the specific enthalpy (measurement of
the heat content of the medium.)
Format
9
9.9
9.99
9.999
Number of decimal points with which the above values are to
be indicated in the display.
gal/bbl
31,5 (US), 42,0 (US), 55,0
(US), 36,0 (Imp), 42,0
(Imp), user def.
31,0
Definition of the value of the used gal/bbl.
US: US-Standard
Imp: XX-Standard
user defined: Freely selectable calculation factor allowed.
Содержание RMS621
Страница 1: ...BA127R 09 en 08 04 510 04788 Software Version 2 0 Operating manual RMS 621 Energy manager ...
Страница 6: ...RMS 621 6 Endress Hauser ...
Страница 23: ...RMS 621 5 Operation Endress Hauser 23 5 1 2 Display Quick Setup ...
Страница 88: ......
Страница 90: ...www endress com worldwide BA 127R 09 en 08 04 510 04788 FM SGML6 0 ...