RIA16
Operating the field indicator
Hauser
35
5.3 Operating matrix
Menu
Operating function
Operating function
Operating function
Parameter
Default /
Choice
Parameter
Default /
Choice
Parameter
Default /
Choice
Analog input
INPUT
Curve
CURV
Signal damping
DAMP
Dec. point of measured val.
DI DP
Linear
Quadratic
LINAR
SQRT
0 to 99 s
0
99.999
999.99
9999.9
99999
3 DEC
2 DEC
1 DEC
0 DEC
Scaling measured val. 4 mA
DI LO
Scaling measured val. 20 mA
DI HI
Measured value offset
OFFST
-9999 to
99999
0.0
-9999 to
99999
100.0
-9999 to
99999
0.0
Display
DISPL
Dimension
DIM
Dimension**
DTEXT
none
%
User-defined
NO
%
TEXT
XXXXX
Limit
LIMIT
Operating mode
MODE
Switching setpoint
SETP
off
Min.safety
with alarm
Max.safety
with alarm
Alarm
OFF
MIN
MAX
ALARM
-9999 to
99999
0.0
Hysteresis
HYST
Response delay
DELY
-9999 to
99999
0.0
0-99 s
0
*) only if “Edit” has been selected for NAMUR
**) only if “TEXT” has been selected for DIMENSION
***) only available for service personnel