Operating the field indicator
RIA16
36
Hauser
5.4 Configuration via interface & FieldCare Device Setup PC
configuration software
WARNING
!
The device must be configured outside the hazardous area.
NOTICE
The device can assume undefined states while configuring with FieldCare! This can result in the
undefined switching of outputs and relays.
To configure the device with the FieldCare Device Setup software, connect the device to your PC.
You need a special interface adapter for this purpose - the Commubox FXA291 (see Chapter
’Accessories’).
The 4-pin connector of the interface cable must be plugged into the corresponding socket inside
the device and the USB connector must be plugged into a free USB slot on the PC.
Connection establishment
When connecting the device, the device DTM is not automatically loaded in FieldCare, i.e. the
device has to be added manually.
Operating
parameters
PARAM
User code
CODE
Program name
PNAME
Firmware version
FWVER
0000 to 9999 0000
NAMUR
NAMUR
NAMUR 3.6
*
N_360
NAMUR 3.80*
N_380
Default
Edit
dEF
Edit
0 to NAMUR
20.5
3.60
NAMUR 3.6
to NAMUR
20.5
3.80
NAMUR 20.5
*
N2050
NAMUR 21.0*
N2100
Test
TEST
NAMUR 3.80
to NAMUR
21.0
20.50
NAMUR 20.5
to 25 mA
21.00
off
Open Collect.
Display
OFF
OUT
DISP
Service
SERV
Service code
SCODE
Parameter reset***
PRSET
- - - -
Yes
No
Yes
No
Menu
Operating function
Operating function
Operating function
Parameter
Default /
Choice
Parameter
Default /
Choice
Parameter
Default /
Choice
*) only if “Edit” has been selected for NAMUR
**) only if “TEXT” has been selected for DIMENSION
***) only available for service personnel