Matrix group
Function group
Item
Access
code
Short description
Default vaule
Set
Select
Display
Possible settings,
selections, or displays
Index No,
GVH
STATIC MATRIX
(This word is not
shown)
MEASURED VALUE 2
LIQUID TEMP.
0
If a temperature bulb is connected, then this position shows
the measured liquid temperature. Otherwise the LCD will be
blank.
0.0 °C
Display
-49.9 ... 249.9 °C
010
GAS TEMPERATURE
0
If a temperature bulb is connected, then this position shows
the measured gas temperature.
0.o °C
Display
-49.9 ... 249.9 °C
013
MORE FUNCTION
MATRIX OF
0
Selection of the dynamic matrix of the programming matrix
CALIBRATION Select
CALIBRATION
DEVICE DATA
SERVICE
TEMPERATURE
HART DEVICE (1)
HART DEVICE (2)
ADJ. SENSOR
030
(Calendar)
0
Calendar and clock without daylight saving system.
NOT TRANSFERRED BY RACKBUS.
Japanese
local time
Display
e.g. 1 410 19:10:41
Year Month Day
HH:MM:SS
033
DIAGNOSTIC CO
0
Self diagnosis at the moment
Display
Error message (refer to
attached table)
036
(Erroneous Message)
0
Previous alarm with message.
Only the last alarm code is transmitted by Rackbus.
(Erroneous
Date)
Display
Error message
(refer to attached table)
037
ACCESS CODE
0
Access code for programming (see Sec. 10.4)
0
Set
0 ... 9999
039
SERVICE
SYSTEM DATA
CONNECTION NMT
51
Connection of the Prothermo NMT538
OFF
Select
OFF
SPOT (three wire RTD
input)
Average (NMT538)
362
5
Op
era
tion
w
ith
the
Pros
erv
o
N
M
S53