Prosonic Flow 92
11 Description of device functions
Hauser
73
Site Setup
Low Flow Cut-Off
Use this function to assign a value to the switch-on point for low flow cut-off. Low flow cut-off is active if
the value entered is not equal to 0.
User input:
5-digit floating-point number
Factory setting:
0.010 m/s
Site Setup
Totalizer
Totalizer Mode
Use this function to define how the flow components are to be totalled by the
totalizer in question.
Options:
OFF – CONTINUOUS – QUICK TIMER – TIMER
OFF
If the totalizer setting OFF is selected and the ENT key pressed, a totalizer
function is switched off.
CONTINUOUS
If the totalizer setting CONTINUOUS is selected and the ENT key pressed,
the +TOTALIZER and -TOTALIZER totalizer displays are started.
QUICK TIMER
If the totalizer setting QUICK TIMER is selected and the ENT key pressed,
successive time units (hh:mm) appear which can be selected for a totalizer
process for a limited time:
00:30 – 01:00 – 01:30 – 02:00 – 02:30 – 03:00
TIMER
If the totalizer setting TIMER is selected and the ENT key pressed, the start
and finish values of a pre-programmed totalizer process can be entered:
START DATE/TIME – END DATE/TIME – START TIMER
If the timer function STAR TIMER is selected and the ENT key pressed, the
pre-programmed totalizer process is started.
Factory setting:
OFF
Preset Totalizer
Use this function to define a starting value for the totalizer.
User input:
Definable range 0000000...9999999
Factory setting:
0
Unit Totalizer
The unit selected will be used for displaying a totalizer value in the group
“MEASUREMENT”.
Metric options:
mL – L – m3 – Km3 – Mm3 – mBBL – BBL – KBBL
US options:
gal – Kgal – ft3 – Kft3 – Mft3 – mBBL – BBL – KBBL
Factory setting:
mL
Содержание prosonic flow 92
Страница 4: ...Brief operating instructions Prosonic Flow 92 4 Endress Hauser...
Страница 12: ...2 Identification Prosonic Flow 92 12 Endress Hauser...
Страница 26: ...3 Installation Prosonic Flow 92 26 Endress Hauser...
Страница 34: ...4 Wiring Prosonic Flow 92 34 Endress Hauser...
Страница 40: ...5 Operation Prosonic Flow 92 40 Endress Hauser...
Страница 46: ...7 Maintenance Prosonic Flow 92 46 Endress Hauser...
Страница 96: ...Index Prosonic Flow 92 96 Endress Hauser...