Proline Promass 84F, 84M
54
Hauser
Promass M:
a0002536
Rupture disk
Sensor housings with integrated rupture disks are optionally available.
#
Warning!
• Make sure that the function and operation of the rupture disk is not impeded through the installation.
Triggering overpressure in the housing as stated on the indication label. Take adequate precautions to ensure
that no damage occurs, and risk to human life is ruled out, if the rupture disk is triggered.
Rupture disk: Burst pressure 10 to 15 bar.
• Please note that the housing can no longer assume a secondary containment function if a rupture disk is used.
• It is not permitted to open the connections or remove the rupture disk.
"
Caution!
• Rupture disks can not be combined with separately available heation jacket.
• The existing connection nozzles are not designed for a rinse or pressure monitoring function.
!
Note!
• Before commissioning, please remove the transport protection of the rupture disk.
• Please note the indication labels.
A0008361
Promass F DN 8 to DN 150
1 = Indication label for the rupture disk, 2 = Transport protection, 3 = ½" NPT internal screw thread with 1" width across
flats
DN
L
H
G
8
85
44.0
½"-NPT
15
100
46.5
25
110
50.0
40
155
59.0
50
210
67.5
80
210
81.5
All dimensions in [mm]
G
L
L
H
2
1
3