Proline Promag H 300
Hauser
25
Modbus RS485
Supply voltage
Input/output 1
Input/output 2
Input/output 3
1 (+)
2 (–)
26 (B)
27 (A)
24 (+)
25 (–)
22 (+)
23 (–)
The terminal assignment depends on the specific device version ordered → 11.
Terminal assignment of the remote display and operating module: → 26
Device plugs available
Device plugs may not be used in hazardous areas!
Device plugs are only available for the following device versions:
Order code for "Input; output 1"
• Option GA "PROFIBUS PA" → 25
• Option SA "FOUNDATION Fieldbus" → 25
Order code for "Input; output 1", option GA "PROFIBUS PA"
Order code for
"Electrical connection"
Cable entry
2
Cable entry
3
L, N, P, U
Plug M12 × 1
–
Order code for "Input; output 1", option SA "FOUNDATION Fieldbus"
Order code for
"Electrical connection"
Cable entry
2
Cable entry
3
M, 3, 4, 5
7/8" plug
–
Pin assignment, device plug
PROFIBUS PA
1
2
4
3
Pin
Assignment
Coding
Plug/socket
1
+
PROFIBUS PA +
A
Plug
2
Grounding
3
-
PROFIBUS PA –
4
Not assigned
FOUNDATION Fieldbus
1
2
4
3
Pin
Assignment
Coding
Plug/socket
1
+
A
Plug
2
-
Signal –
3
Grounding
4
Not assigned
Supply voltage
Order code for
"Power supply"
terminal voltage
Frequency range
Option
D
DC 24 V
±20%
–
Option
E
AC100 to 240 V –15…+10%
50/60 Hz, ±4 Hz
Option
I
DC 24 V
±20%
–
AC100 to 240 V –15…+10%
50/60 Hz, ±4 Hz
Содержание Proline Promag H 300