PROline Promag 10 P
Hauser
4
Electrical connection, remote
version
a
Cover of the connection compartment
b
Cover of the sensor connection housing
c
Signal cable
d
Coil current cable
n.c.
Not connected, isolated cable shields
Supply voltage
85 to 250 VAC, 45 to 65 Hz
20 to 28 VAC, 45 to 65 Hz / 11 to 40 VDC
Power supply and signal cable (outputs):
• 1/2” NPT
Connecting cable for remote version:
• 1/2” NPT
Coil cable:
• 2 x 18 AWG (0.75 mm
2
) PVC cable with common, braided copper shield,
approximately 0.28” diameter (Ø approx. 7 mm)
• Conductor resistance:
≤
0.011
Ω
/ft (37
Ω
/km)
• Capacitance: core/core, shield grounded:
≤
36 pF/ft (120 pF/m)
• Permanent operating temperature: -5° to +180°F (–20 to +80°C)
Signal cable:
• 3 x 20 AWG (0.38 mm
2
) PVC cable with common, braided copper shield,
approximately 0.28” diameter (Ø approx. 7 mm) and individually shielded cores.
• With Empty Pipe Detection (EPD): 4 x 20 AWG (0.38 mm
2
) PVC cable with
common, braided copper shield, approximately 0.28” diameter (Ø approx. 7 mm)
and individually shielded cores.
• Conductor resistance:
≤
0.015
Ω
/ft (50
Ω
/km)
• Capacitance: core/shield:
≤
128 pF/ft (420 pF/m)
• Permanent operating temperature: -5° to +180°F (-20 to +80 °C)
• Conductor cross-section: maximum 0.004 in
2
(2.5 mm
2
)
Cable entry
Cable specifications
6
5
5
7
7
8
4
4
37
37
36
Electrode circuit
Coil circuit
42
42
41
41
E1 E2 GND E
2
1
a
c
d
b
S1 E1 E2 S2GND E S
Esc
E
-
+
n.c.
n.c.
n.c.
br
n
wht
gr
n
ye
l
EPD
Pipe
Meas.signal