Electromagnetic flow
measuring system
PROline promag 10 P

Flow measurement in chemical
or process applications

Technical
Information
TI 094D/24/ae

Application

Electromagnetic flowmeter for measuring
liquids with a minimum conductivity of
50 

µ

S/cm, such as:

• Acids or alkalis
• Chemically loaded wastewater
• Paints
• Sewage sludge

Nominal diameters from 1” to 12”
Maximum fluid temperature:
PTFE:  265°F (130°C)
Sensor fitting lengths to ISO and DVGW

Features and benefits

• Ideal for simple measuring tasks -

current output for displaying the
current flow, pulse output for driving
an external totalizer or as status
output

• Guaranteed safety of application -

Promag 10 offers all basic functions
to guarantee a high degree of
reliability and measured value stability

• Optimum process control based on an

accuracy of ± 0.5%

• PTFE lining guarantees maximum

resistance in the case of aggressive
fluids and temperatures up to 265°F

• Used in difficult conditions (in shafts,

areas with vibration, or permanently
under water) - the sensor can be
installed separate from the transmitter
and is availalbe with NEMA 6P (IP 68)
protection.

• Service friendly - functional design

makes maintenance work easier -
HART

®

, Fieldtool and FieldCheck

provide support right down to device
verification without the need for sensor
removal.

The Power of Know How

Содержание PROline promag 10 P

Страница 1: ...t for driving an external totalizer or as status output Guaranteed safety of application Promag 10 offers all basic functions to guarantee a high degree of reliability and measured value stability Opt...

Страница 2: ...Q A v Ue induced voltage B magnetic induction magnetic field L electrode gap v flow velocity Q volume flow A pipe cross section I current strength The measuring system consists of a transmitter and a...

Страница 3: ...ally isolated from each other Output signal Load Signal on alarm Low flow cutoff Galvanic isolation Output Power supply Electrical connection measuring unit a Cable for power supply 85 to 250 VAC 20 t...

Страница 4: ...grounded 36 pF ft 120 pF m Permanent operating temperature 5 to 180 F 20 to 80 C Signal cable 3 x 20 AWG 0 38 mm2 PVC cable with common braided copper shield approximately 0 28 diameter approx 7 mm a...

Страница 5: ...t 28 VAC maximum 16 A 5 ms at 250 VAC Lasting minimum 1 2 power cycle EEPROM retain the measuring system data in the event of a power supply failure Power consumption Power supply failure Potential eq...

Страница 6: ...pipes and lined pipes Normally potential is matched using the reference electrodes in the measuring tube However in exceptional cases it is possible that due to the grounding plan of a system large ma...

Страница 7: ...d Also comply with the regulations applicable to potential free installation 1 isolating transformer 2 electrically insulated Performance characteristics To DIN 19200 and VDI VDE 2641 Medium temperatu...

Страница 8: ...isk of damage to the lining of the measuring tube It might be necessary to install pulse dampers in systems incorporating reciprocat ing diaphragm or peristaltic pumps The sensor is shock and vibratio...

Страница 9: ...for correct measuring of problematic mediums Horizontal orientation The measuring electrode plane should be horizontal This prevents brief insulation of the two electrodes by entrained air bubbles Cau...

Страница 10: ...tlet runs If possible install the sensor well clear of fittings such as valves T pieces elbows etc Compliance with the following requirements for the inlet and outlet runs is necessary in order to ens...

Страница 11: ...temperature 5 to 140 F 20 to 60 C for sensor and transmitter Install the device at a shady location Avoid direct sunlight particularly in warm climatic regions 15 to 120 F 10 to 50 C 70 F 20 C is the...

Страница 12: ...Measuring Resistance to partial vacuum tube lining of measuring tube lining Limit values for abs pressure psia at various fluid temperatures 75 F 175 F 212 F 265 F 1 PTFE 0 0 0 1 4 1 1 2 PTFE 0 0 0 1...

Страница 13: ...10 remote transmitter mounting A Direct wall mounting B Pipe mounting Esc E ANSCHLUSSKLEMMEN FIELD TERMINALS 4 49 113 7 01 178 5 31 135 3 94 100 3 94 100 5 91 150 4 76 121 0 78 1 18 20 30 6 34 7 13 1...

Страница 14: ...19 7 200 200 200 200 250 300 350 450 500 331 331 331 381 381 462 517 567 617 247 247 247 272 272 312 337 362 387 9 72 9 72 9 72 10 7 10 7 12 3 13 3 14 2 15 2 3 31 3 31 3 31 4 29 4 29 5 90 7 08 8 07 9...

Страница 15: ...336 336 417 472 522 572 202 202 202 227 227 267 292 317 342 7 95 7 95 7 95 8 94 8 94 10 5 11 5 12 5 13 5 A in mm B in mm C in mm K in mm E in mm Weight lb kg Nominal Size 1 1 1 2 2 3 4 6 8 10 12 25 4...

Страница 16: ...22 Seal Seals to DIN 2690 Ground disks 316L SS or Alloy C 22 0 59 15 0 39 10 Nominal size 1 0 08 2 H B A D 0 26 6 5 1 1 1 2 2 3 4 6 8 10 12 2 1 18 1 75 2 22 3 35 4 33 6 42 8 29 10 4 12 5 30 44 5 56 5...

Страница 17: ...aboratory Procedures EN 61326 IEC 1326 Emmision to class A requirements Electromagnetic compatibility EMC require ments ANSI ISA S82 01 Safety Standards for Electrical and Electronic Test Measuring Co...

Страница 18: ...Hauser are available for the transmitter and the sensor Contact your local representative or Endress Hauser for detailed information Supplemental documentation Technical Information Promag 10 W TI 09...

Страница 19: ...7 Approvals A For use in nonhazardous area R FM approved non incendive Class I Division 2 CSA Class I Division 2 8 Protection type A NEMA 4X IP 67 compact aluminum field housing G NEMA 4X IP 67 remote...

Страница 20: ...el Pedregal 01900 Mexico D F Mexico Phone 525 568 2405 FAX 525 568 7459 For application and selection assistance in the U S call 888 ENDRESS For total support of your installed base 24 hours a day in...

Отзывы: