Electrical connection
Flowmeter Proline 500 – digital
16
Hauser
5.2.3
Connecting cable
Non-hazardous area, Ex Zone 2, Class I, Division 2
Standard cable
A standard cable can be used as the connecting cable.
Standard cable
4 cores (2 pairs); pair-stranded with common shield
Shielding
Tin-plated copper-braid, optical cover ≥ 85 %
Loop resistance
Power supply line (+, –): maximum 10 Ω
Cable length
Maximum 300 m (1
000 ft), see the following table.
Cross-section
Cable length
0.34 mm
2
(AWG 22)
80 m (270 ft)
0.50 mm
2
(AWG 20)
120 m (400 ft)
0.75 mm
2
(AWG 18)
180 m (600 ft)
1.00 mm
2
(AWG 17)
240 m (800 ft)
1.50 mm
2
(AWG 15)
300 m (1
000 ft)
Hazardous area, Ex Zone 1, Class I, Division 1
Standard cable
A standard cable can be used as the connecting cable.
Standard cable
4, 6, 8 cores (2, 3, 4 pairs); pair-stranded with common shield
Shield
Tin-plated copper braid, optical cover ≥ 85 %
Capacitance C
Maximum 760 nF IIC, maximum 4.2 µF IIB
Inductance L
Maximum 26 µH IIC, maximum 104 µH IIB
Inductance/resistance ratio
(L/R)
Maximum 8.9 µH/Ω IIC, maximum 35.6 µH/Ω IIB (e.g. according to IEC 60079-25)
Loop resistance
Power supply line (+, –): maximum 5 Ω
Cable length
Maximum 150 m (500 ft), see the following table.